Siemens SIRIUS 3RT Manual page 302

Industrial controls, switching devices, contactors / contactor assemblies
Hide thumbs Also See for SIRIUS 3RT:
Table of Contents

Advertisement

Accessories
9.4 Surge suppressor
Technical background information
The oscillograms below show what happens when contactor coils are disconnected without
and with overvoltage attenuation.
Coil without RC circuit
Figure 9-8
Oscillogram of the disconnection of a contactor relay coil; the coil does not have an RC
circuit: Shower discharges are clearly visible (voltage peaks up to several kV). Once the
disconnection process has started, the shower discharges occur for about 250 μs; after that,
the vibration is simply damped.
302
Disconnection of a contactor coil without RC circuit
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006