⑩
⑪
⑫
⑬
⑭
⑮
SIRIUS - SIRIUS 3RT Contactors/Contactor assemblies
Manual, 09/2017, A5E03656507120A/RS-AE/006
Turn the two release levers back.
Remove the two release levers.
Screw the cable bands tight to the interrupters with the Allen key.
Tightening torque: 7.5 ... 8.5 Nm
Screw the cable bands tight to the interrupters with the Allen key.
Tightening torque: 4.4 ... 5.2 Nm
Attach the enclosure top part.
Tighten the 4 hexagon socket-head screws on the front plate.
7.5 Replacing the vacuum interrupters (sizes S10 and S12)
Mounting
225