Wiring
3.4
Terminal assignment
3.5
Cable specification FOUNDATION Fieldbus
Twisted, shielded pairs must be used. The cable specifications can be taken from the FF
specification or IEC 61158-2. The following have been found suitable:
• Siemens 6XV1 830-5BH10
• Kerpen CEL-PE/OSCR/PVC/FRLA FB-02YS(ST)YFL
• Belden 3076F
3.6
Connecting the measuring unit
Ground connection
It is necessary to make a good ground connection to the ground terminal on the outside of the
housing, in order to achieve EMC security.
Terminals
For wire cross-sections of 0.5 to 2.5 mm
Cable entry
• Cable gland: M20x1.5
• Cable entry: G½ or ½NPT
• FOUNDATION Fieldbus 7/8" plug
20
Levelflex M FMP40 FOUNDATION Fieldbus
plant ground
1 2
3 4
FF- FF+
2
L00-FMP4xxxx-04-00-00-en-004
Endress+Hauser