Advertisement

Levelflex M FMP40 FOUNDATION Fieldbus
5.4.5 Function "process propert." (004)
ENDRESS + HAUSER
+
E
Use this function to adapt the device reaction to the filling speed in the tank. The setting impacts
on an intelligent filter.
Selection:
• standard
• fast change
• slow change
• test:no filter
Selection:
Application:
2-wire
electronics:
5.4.6 Function "end of probe" (030)
ENDRESS + HAUSER
+
E
Use this function to select the polarity of the probe end signal. If the probe end is uncovered or
in an insulated attachment, there is a negative probe end signal.
The signal from the probe end is positive if the attachment is grounded.
Selection:
• free
• tie down isol.
• tie down gnd. (if using a metallic centering of probe end)
Endress+Hauser
standard
fast change
For all normal
Small tanks, primarily
applications, bulk solids
with fluids, at high
and fluids at low to
filling speeds.
medium filling speed
and sufficiently large
tanks.
Dead time: 4 s
Dead time: 2 s
Rise time: 18 s
Rise time: 5 s
slow change
test:no filter
Applications with strong
Shortest reaction time:
surface movement, e.g.
• For test purposes
caused by stirrer,
• Measurement in
primarily large tanks
with slow to medium
filling speed.
Dead time: 6 s
Dead time: 1 s
Rise time: 40 s
Rise time: 0 s
Commissioning
small tanks at high
filling speeds, if
"rapid change"
setting is too slow.