Menu Structure - Danfoss ERC 211 User Manual

Smart multipurpose refrigeration controller erc 21x series
Hide thumbs Also See for ERC 211:
Table of Contents

Advertisement

– STEP 4: select sensor type "o06"
The display automatically shows sensor selection parameter "o06".
Press SET to select the sensor type.
The display shows the default value (eg. "n10" flashing).
Choose sensor type by pressing UP/DOWN (n5=NTC 5 K, n10=NTC 10 K, Ptc=PTC, Pt1=Pt1000) and press SET to confirm.
NOTE: all sensors must be the same type.
– STEP 5: configure DO4 output "o36"
The display automatically shows the "o36" parameter to configure "DO4" output. (Available only in 4 relays model).
Select light "Lig" or alarm "ALA" as per the application and press SET to confirm.
The display returns to normal display mode and the control is started.
5.3|

Menu Structure

1) Parameter groups
Password (if enabled)
Status input
Configuration
14
FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
2) Parameter name
SET
(only for 4 relays model)
Scroll through the
parameter groups
SET: press for 3 seconds to access
status, setup and service
Main switch
Application
Sensor type
Scroll through the
parameter names
DO4 configuration
3) Value
Application
1-2-3-4-5-6
SET
Application 0
Application
1-2-3-4-5-6