Parameter name - ERC 214
Defrost
Defrost method
no=no defrost, nAt=natural,
EL=electrical, gAS=hot gas
Defrost stop temperature
Defrost interval
Max defrost time
Defrost delay at power up
(or DI signal)
Drip delay
Fan delay after defrost
Fan start temperature
after defrost
Fan during defrost
Defrost stop sensor
configuration non=time,
Air=Sair (air temperature),
dEF=S5 (defrost sensor)
Compressor accumulated
runtime to start defrost
0=OFF
Defrost on demand
20.0=OFF
Defrost delay after pull-down
0=OFF
Fan control
Fan at compressor cutout
FFc=fan follow compressor,
FAo=fan always ON,
FPL= fan pulsating
Fan stop evaporator
temperature
50.0=OFF
Fan ON cycle
Fan OFF cycle
Compressor
Compressor minimum ON time
Compressor minimum OFF time
Compressor OFF delay
at door open
Zero crossing selection
Note: hidden parameters are greyed out
30
FR · ERC 21X user manual · DKRCC.ES.RL0.H3.02/520H9656 · ©Danfoss
Code
Min
Max
Unit
d--
d01
no
gAS
d02
0.0
50.0
C/F
d03
0
240
hours
d04
0
480
min
d05
0
240.0
min
d06
0
60
min
d07
0
60
min
d08
-50.0
0.0
C/F
d09
oFF
on
d10
non
dEF
d18
0
96
hours
d19
0.0
20.0
K
d30
0
960
min
F--
F01
FFc
FPL
F04
-50.0
50.0
C/F
F07
0
15
min
F08
0
15.0
min
c--
C01
0
30
min
C02
0
30
min
C04
0
15
min
C70
no
yES
App. 0
App. 1 App. 2 App. 3 App. 4 App. 5 App. 6
(Def.)
EL
nAt
EL
6.0
-
-
8
6
8
30
45
15
0
0
0
0
0
0
0
0
0
-5.0
-
-
on
on
on
non
non
non
non
0
0
0
20.0
-
-
0
0
0
FAo
FAo
FAo
FAo
50.0
-
-
2
2
2
2
2
2
0
0
0
2
2
2
0
0
0
yES
yES
yES
yES
EL
EL
EL
EL
-
6.0
6.0
6.0
12
8
12
8
15
30
30
30
0
0
0
-
0
0
0
5
0
0
0
5
-
-5.0
-5.0
-
on
on
on
on
dEF
dEF
non
0
0
0
-
-
20.0
20.0
-
0
0
0
-
FAo
FAo
FAo
-
50.0
50.0
-
2
2
2
2
2
2
2
2
0
0
0
0
2
2
2
2
0
0
0
1
yES
yES
yES