Installation guide - ERC 211

4 - Menu structure

1) Parameters group
Password (if enabled)
Input states
Configuration
parameter groups
5 - Quick configuration with "cFg" menu
• Press SET for three seconds to open the parameter groups.
• Select the "cFg" menu and press SET to open. The first menu "r12" (main switch) is displayed.
• Set the main switch to OFF (r12=0) to change the preinstalled application.
• Press UP/DOWN to scroll through the parameters list.
• Configure the parameter "o61" to select a preinstalled application:
- Press SET to open the parameter "o61".
- Press UP/DOWN to select an application (AP0= no application).
- Press SET to confirm; "o61" is displayed.
• Continue to set the following parameters (sensor type "o06") in the "cFg" menu.
© Copyright Danfoss | Published by ADAP-KOOL | 2018.10
SET: press for 3 seconds for state, settings and service
2) Parameter names
SET
To scroll the
Main switch
Application
To scroll the
parameter names
Sensor type
Installation guide | ERC 211
3) Value
Application
1-2-3-4-5
SET
Application 0
Application
5-4-3-2-1
DKRCE.PI.RL0.P4.02 | 3