Commissioning - Stuart Turner CH 4-30 B Installation, Operation & Maintenance Instructions Manual

50 hz
Table of Contents

Advertisement

5 COMMISSIONING / SYSTEM FLUSHING/ PRIMING / STARTING
5.11 System Flushing: The pipework system should be flushed out
5.12 Water Supply: Always ensure that water storage capacity is adequate to meet
the demand. Ensure the pump chamber is full of water before starting the
pump. Failure to do this could result in seal damage. To ensure dry running
does not occur the pump must be primed as described in priming section below.
Do not run pump dry.
5.13 Priming:
The pump must be primed (filled with water) before starting.
Turn on the service valves and vent/prime pump head.
(a) Loosen priming plug and allow an even flow of water this may take a
few seconds.
(b) Re-seal draining plug, nipping tight. The pump is now ready to start.
Note: This image is for
reference only
5.14 Starting:
a) Ensure all outlets are closed, turn power supply 'on' - pump will start,
pressurise the system then stop.
b) Open and close all outlets in turn associated with the pump, (including w/c
systems) allowing water to flow from each outlet until all air is purged. As
each outlet is opened and closed, the pump will start and stop respectively.
Note: After closing the outlet there will be a small time delay before the
pump stops, which is normal.
c) Any tap or control valve within the system when opened and closed will now
turn the pump on/off. Providing this is the case the system is now operating
correctly.
d) Carefully check pump and pipework for leaks whilst pump running and
stationary before leaving the installation unattended.
5.15 For Further Technical Support: Phone the Stuart Turner PumpAssist team
on +44 (0) 800 31 969 80. Our staff are trained to help and advise you over the
phone.
prior to the pump being connected to ensure any contaminants/
chemical residues and foreign bodies are removed from elsewhere
in the system.
Never operate pump with inlet and/or outlet isolating valves in
the closed position. Damage will occur!
Fig. 12
- 15 -
Priming
Plug
Vent
Plug

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents