Oscillography - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

PRODUCT SETUP
5.3.7.4 Local time
SETTINGS  PRODUCT SETUP  REAL TIME CLOCK  LOCAL TIME
 LOCAL TIME
5
The C30 maintains two times: local time and Universal Coordinated Time (UTC). Local time can be provided by IRIG-B
signals. UTC time is provided by SNTP servers.
The real-time clock (RTC) and time stamps reported in historical records and communication protocols can be incorrect if
the Local Time settings are not configured properly.
See the IRIG-B section in the Installation chapter for guidance on these settings when using an IRIG-B source that sets the
IRIG-B control bits according to IEEE Std 1344-1995.
LOCAL TIME OFFSET FROM UTC
zones in the eastern hemisphere have positive values; time zones in the western hemisphere have negative values. A value
of zero causes the relay to use UTC for local time. This setting has two uses. When the system RTC is synchronized with a
communications protocol providing only local time or it is free-running, the offset setting is used to calculate UTC from the
local time these provide. When the RTC is synchronized with a communications protocol providing only UTC (such as PTP or
SNTP), the time offset setting is used to determine local time from the UTC provided. PTP
ALTERNATE_TIME_OFFSET_INDICATOR TLVs are not used to calculate local time.
DAYLIGHT SAVINGS TIME
when IRIG-B time synchronization is active, the local time in the IRIG-B signal contains any daylight savings time offset and
so the DST settings are ignored.

5.3.8 Oscillography

5.3.8.1 Menu
SETTINGS  PRODUCT SETUP  OSCILLOGRAPHY
 OSCILLOGRAPHY
5-108
LOCAL TIME OFFSET
FROM UTC: 0.0 hr
DAYLIGHT SAVINGS
TIME: Disabled
DST START MONTH:
January
DST START DAY:
Sunday
DST START DAY
INSTANCE: First
DST START HOUR:
2:00
DST STOP MONTH:
January
DST STOP DAY:
Sunday
DST STOP DAY
INSTANCE: First
DST STOP HOUR:
2:00
— Used to specify the local time zone offset from UTC (Greenwich Mean Time) in hours. Time
and
— Can be used to allow the relay to follow the DST rules of the local time zone. Note that
DST
NUMBER OF RECORDS:
15
TRIGGER MODE:
Automatic Overwrite
CHAPTER 5: SETTINGS
Range: –24.0 to 24.0 hr in steps of 0.5
Range: Disabled, Enabled
Range: January to December (all months)
Range: Sunday to Saturday (all days of the week)
Range: First, Second, Third, Fourth, Last
Range: 0:00 to 23:00 in steps of one hour
Range: January to December (all months)
Range: Sunday to Saturday (all days of the week)
Range: First, Second, Third, Fourth, Last
Range: 0:00 to 23:00 in steps of one hour
Range: 1 to 64 in steps of 1
Range: Automatic Overwrite, Protected
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents