CHAPTER 5: SETTINGS
Operand type
Operand syntax
LED INDICATORS:
LED IN SERVICE
Graphical front panel
LED TROUBLE
LED TEST MODE
LED TRIP
LED ALARM
LED PICKUP
LED VOLTAGE
LED CURRENT
LED FREQUENCY
LED OTHER
LED PHASE A
LED PHASE B
LED PHASE C
LED NEUTRAL/GROUND
LED INDICATORS:
LED TEST IN PROGRESS
LED test
LED INDICATORS:
LED USER 1
User-programmable
LEDs
Enhanced and
standard front panels
LED USER 2 to 48
LED INDICATORS:
EVENT CAUSE LED 1
User-programmable
EVENT CAUSE LED 2 to 9
LEDs
Graphical front panel
PASSWORD
ACCESS LOC SETG OFF
SECURITY
ACCESS LOC SETG ON
ACCESS LOC CMND OFF
ACCESS LOC CMND ON
ACCESS REM SETG OFF
ACCESS REM SETG ON
ACCESS REM CMND OFF
ACCESS REM CMND ON
UNAUTHORIZED ACCESS
RxGOOSE
RxGOOSE 1 On
RxGOOSE 64 On
RxGOOSE 1 Off
RxGOOSE 64 Off
R-RxGOOSE1 IGMP On
R-TxGOOSE1 ARP On
<RxGOOSE Boolean1 ID> On
<RxGOOSE DPS1 ID> Bad
<RxGOOSE DPS1 ID> Interm
<RxGOOSE DPS1 ID> Off
<RxGOOSE DPS1 ID> On
RESETTING
RESET OP
RESET OP (COMMS)
RESET OP (OPERAND)
RESET OP (PUSHBUTTON)
RESET ANCTR OP
RESET ANCTR OP(OPRD)
RESET ANCTR OP(MNUL)
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
Operand description
Asserted when the front panel IN SERVICE LED is on
Asserted when the front panel TROUBLE LED is on
Asserted when the front panel TEST MODE LED is on
Asserted when the front panel TRIP LED is on
Asserted when the front panel ALARM LED is on
Asserted when an element picks up and to turn Event Cause LED 1 on by
default
Asserted when a voltage element involved and to turn Event Cause LED 2 on
by default
Asserted when a current element involved and to turn Event Cause LED 3 on
by default
Asserted when a frequency element involved and to turn Event Cause LED 4
on by default
Asserted when a composite element involved and to turn Event Cause LED 5
on by default
Asserted when phase A involved and to turn Event Cause LED 6 on by default
Asserted when phase B involved and to turn Event Cause LED 7 on by default
Asserted when phase C involved and to turn Event Cause LED 8 on by default
Asserted when a neutral or ground element involved and to turn Event Cause
LED 9 on by default
An LED test has been initiated and has not finished
Asserted when user-programmable LED 1 is on
The operand above is available for user-programmable LEDs 2 through 48
Asserted when event cause LED 1 is on
Same operand as EVENT CAUSE LED 1
Asserted when local setting access is disabled
Asserted when local setting access is enabled
Asserted when local command access is disabled
Asserted when local command access is enabled
Asserted when remote setting access is disabled
Asserted when remote setting access is enabled
Asserted when remote command access is disabled
Asserted when remote command access is enabled
Asserted when a password entry fails while accessing a password protected
level of the C30
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Flag is set, logic=1
Indicates status of IGMP connection for R-GOOSE multicast reception
Indicates status of ARP connection for R GOOSE unicast transmission
Replace bracketed text with RxGOOSE Boolean1 status of "true"
Replace bracketed text with RxGOOSE DPS1 status of "bad-state"
Replace bracketed text with RxGOOSE DPS1 status is "intermediate-state"
Replace bracketed text with RxGOOSE DPS1 status is "off"
Replace bracketed text with RxGOOSE DPS1 status is "on"
Reset command is operated (set by all three operands below)
Communications source of the reset command
Operand (assigned in the INPUTS/OUTPUTS  RESETTING menu) source of
the reset command
Reset key (pushbutton) source of the reset command
Reset annunciator command is operated (set by any operands below)
Reset operand (assigned in INPUTS/OUTPUTS  RESETTING
ANNUNCIATOR menu) source of the reset annunciator command
Reset manual (pushbutton or EnerVista software) source of the reset
annunciator command