GE C30 Instruction Manual page 403

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

CHAPTER 6: ACTUAL VALUES
TM
There are 256 FlexState
bits available. The second line value indicates the state of the given FlexState bit.
6.3.13 Ethernet
ACTUAL VALUES  STATUS  ETHERNET
 ETHERNET
These values indicate the status of the first, second, and third Ethernet links.
6.3.14 Real time clock synchronizing
ACTUAL VALUES  STATUS  REAL TIME CLOCK SYNCHRONIZING
 REAL TIME CLOCK
 SYNCHRONIZING
actual value is the time synchronizing source the relay is using at present. Possible sources are: Port 1
RTC SYNC SOURCE
PTP Clock, Port 2 PTP Clock, Port 3 PTP Clock, IRIG-B, Other, and None, where "Other" means any less precise source (SNTP,
IEC 103, IEC 104, or DNP). An actual value displays when the relay includes the IEEE 1588 software option.
The
is the grandmasterIdentity code being received from the present PTP grandmaster, if any. When the
GRANDMASTER ID
relay is not using any PTP grandmaster, this actual value is zero. The grandmasterIdentity code is specified by PTP to be
globally unique, so one can always know which clock is grandmaster in a system with multiple grandmaster-capable
clocks.
is the estimated maximum time error at present in the RTC, considering the quality information imbedded in the
ACCURACY
received time signal. The value 999,999,999 indicates that the magnitude of the estimated error is one second or more, or
that the error cannot be estimated.
is the present state of the port's PTP clock. The PTP clock state is:
PORT 1...3 PTP STATE
Disabled is the port's function setting is Disabled
No Signal if enabled but no signal from an active master has been found and selected
Calibrating if an active master has been selected but lock is not at present established
Synch'd (No Pdelay) if the port is synchronized, but the peer delay mechanism is non-operational
Synchronized if synchronized
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
ETHERNET PRI LINK
STATUS: Fail
ETHERNET SEC LINK
STATUS: Fail
ETHERNET TER LINK
STATUS: Fail
RTC SYNC SOURCE:
None
GRANDMASTER ID:
0X0000000000000000
ACCURACY:
999999999 ns
PORT 1 PTP STATE:
No Signal
PORT 2 PTP STATE:
No Signal
PORT 3 PTP STATE:
No Signal
PTP - IRIG-B DELTA:
500000000 ns
Range: Fail, OK
Range: Fail, OK
Range: Fail, OK
Range: see below
Range: any 8 octet value
Range: 0 to 999,999,999 ns
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: Disabled, No Signal, Calibrating, Synch'd (No
Pdelay), Synchronized
Range: -500,000,000 to +500,000,000 ns
STATUS
6
6-7

Advertisement

Table of Contents
loading

Table of Contents