GE C30 Instruction Manual page 294

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

PRODUCT SETUP
The binary input points are mapped using elements from a list of possible FlexLogic operands. A maximum of 96 binary
inputs (points) can be mapped this way.
The IEC 60870-5-103 point list always starts with point 0 and ends at the first "Off" value. Since the IEC 60870-5-103 point
list must be in a continuous block, any points assigned after the first "Off" point are ignored.
For each defined point, set appropriate values for the Function Type (FUN) and Information Number (INF), which form the
Information Object Identifier field of the ASDU, as defined in IEC 60870-5-103.
The binary input points are sent as Class 1 data. They are sent either as a response to a general interrogation received
from the controller or reported spontaneously. Spontaneous transmission occurs as a response to cyclic Class 2 requests.
If the C30 wants to transmit Class 1 data at that time, it demands access for Class 1 data transmission (ACD=1 in the
control field of the response).
For any change to take effect, restart the relay.
SETTINGS  PRODUCT SETUP  COMMUNICATIONS  IEC 60870-5-103  IEC103 INPUTS MEASURANDS
 IEC103 INPUTS
 MEASURANDS
5
 ASDU 1
 ASDU 4
5-100
POINT 95 Input
Off
 ASDU 1
 ASDU 4
ASDU 1 TYP:
9
ASDU 1 FUN:
0
ASDU 1 INF:
0
ASDU 1 SCAN TOUT:
0
ASDU 1 ANALOG 1
Off
ASDU 1 ANALOG 1
FACTOR: 1.000
ASDU 1 ANALOG 1
OFFSET: 0
ASDU 1 ANALOG 9
Off
ASDU 1 ANALOG 9
FACTOR: 1.000
ASDU 1 ANALOG 9
OFFSET: 0
ASDU 4 TYP:
9
ASDU 4 FUN:
0
CHAPTER 5: SETTINGS
Range: FlexLogic operand
See below
Range: 3 or 9
Range: 0 to 255 in steps of 1
Range: 0 to 255 in steps of 1
Range: 0 to 1000 s in steps of 1
Range: FlexAnalog parameter
Range: 0.000 to 65.535 in steps of 0.001
Range: -32768 to 32767 in steps of 1
Range: FlexAnalog parameter
Range: 0.000 to 65.535 in steps of 0.001
Range: -32768 to 32767 in steps of 1
Range: 3 or 9
Range: 0 to 255 in steps of 1
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL