CHAPTER 5: SETTINGS
Home Page Content
Range: Product Information, SLD 1...5, Annunciator, Annunciator 1...8, Phasors 1...6, Tabular 1...5, Event Records, Targets
Default: Product Information
This setting specifies the page to display between the home page header and footer. Pressing the Home button returns
the display to this page. The home page displays for the rolling mode delay specified, then rolls to the rolling mode
pages.
The "Annunciator" option without a page number specifies the first annunciator page in the following sequence:
The first annunciator page that contains an annunciator window that is in alarm (fast flash)
The first annunciator page that contains an annunciator window that is in ringback. Ringback is a "return alert."
Visual and audible signals are given when conditions return to normal, then the sequence returns to normal by
pushing the RESET button.
The first annunciator page that contains an annunciator window that is in abnormal state
Annunciator page 1
Whenever an annunciator window changes state this list is re-evaluated, which can result in the home page displaying
a different annunciator page.
The Tabular option displays a configured actual values/metering page.
The Targets option displays error messages.
Date Format
Range: yyyy-mm-dd, dd-mmm-yy, yyyy/mm/dd, m/d/yyyy, m/d/yy, mm/dd/yy, mm/dd/yyyy, yy/mm/dd
Default: yyyy-mm-dd
This setting specifies the format for dates on the graphical front panel. It applies to the page header, the events records,
the annunciator, and everywhere else a date displays. If the relay is synchronized to an external time source via PTP,
IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow.
yyyy — four-digit year, for example 2017
yy — two-digit year, for example 17 for 2017
mmm — abbreviation of month name, for example Jan for January
mm — two-digit month, for example 01 for January and 10 for October
m — one or two-digit month, for example 1 for January and 10 for October
dd — two-digit day, for example 08 and 28
d — one or two-digit day, for example 8 and 28
To set the date and time, access Synchronize Devices in the software or Settings > Product Setup > Real Time Clock.
Time Format
Range: hh:mm:ss, h:mm:ss tt
Default: hh:mm:ss
This setting specifies the format for time on the graphical front panel. It applies to the page header and everywhere else
a time displays. When the Date Format and the Time Format use the defaults, the date and time are separated by the
character "T" per the ISO convention. Otherwise they are separated by a space. If the relay is synchronized to an external
time source via PTP, IRIG-B, SNTP, and so on, the date/time is shown in white, and otherwise in yellow.
hh — two-digit hour, for example 02 for two o'clock
h — one or two-digit hour, for example 2 for two o'clock
mm — two-digit minute, for example 51 minutes
ss — two-digit second (can have a decimal and further digits appended), for example 16 seconds
tt — AM or PM based on 12 hour clock
If microseconds have to be displayed, for example, in the event records, the 24-hour clock is adopted. The representation
of an accumulated period (for example hh:mm) is not affected by the selected time format.
To set the date and time, access Synchronize Devices in the software or Settings > Product Setup > Real Time Clock.
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL
PRODUCT SETUP
5
5-25

Advertisement

Table of Contents
loading