Transducer Inputs And Outputs - GE C30 Instruction Manual

Controller system
Hide thumbs Also See for C30:
Table of Contents

Advertisement

WIRING
CHAPTER 3: INSTALLATION
Figure 3-22: Active impedance contact input V-I characteristic
3

3.3.6 Transducer inputs and outputs

Transducer input modules can receive input signals from external DCmA output transducers (DCmA In) or resistance
temperature detectors (RTDs). Hardware and software are provided to receive signals from these external transducers and
convert these signals into a digital format for use as required.
Transducer output modules provide DC current outputs in several standard DCmA ranges. Software is provided to
configure virtually any analog quantity used in the relay to drive the analog outputs.
Every transducer input/output module has a total of 24 terminal connections. These connections are arranged as three
terminals per row with a total of eight rows. A given row can be used for either inputs or outputs, with terminals in column
"a" having positive polarity and terminals in column "c" having negative polarity. Since an entire row is used for a single
input/output channel, the name of the channel is assigned using the module slot position and row number.
Each module also requires that a connection from an external ground bus be made to terminal 8b. The current outputs
require a twisted-pair shielded cable, where the shield is grounded at one end only. The following figure illustrates the
transducer module types (5A, 5C, 5D, 5E, and 5F) and channel arrangements that can be ordered for the relay.
3-26
C30 CONTROLLER SYSTEM – INSTRUCTION MANUAL

Advertisement

Table of Contents
loading

Table of Contents