T24-Ta [Temperature Acquisition Pt100] - Mantracourt T24-BSi Technical Manual

T24 series
Hide thumbs Also See for T24-BSi:
Table of Contents

Advertisement

T24-TA [Temperature Acquisition Pt100]

Overview
The remote acquisition module requires an external platinum temperature sensor (Pt100). The module
measures the temperature and periodically transmits it. Between transmissions the device is optionally in a
power saving sleep mode to conserve batteries.
Various devices are available that utilise the transmitted data and include handheld
displays etc
Communications
To configure the device you will use the Read and Write mechanisms described in the Data Packet Structures
section to read and write parameters and execute commands.
Parameter List
Parameter
ID
Version
Channel
EncKey
Power
Name
Model
WakeChkInt
UseCSMA
BattLevel
BattLowLevel
LowPowerMode
TxInterval
SampleTime
SleepDelay
DataTag
43
Mantracourt Electronics Limited T24 Technical Manual
Command
Description
Number
3
Read the unique identifier ID for this device. (3 bytes)
53
Read the firmware version.
11
Radio Channel
15
The radio encryption key to operate on. Requires
power cycle or Reset to enable.
release.
12
Set or read the output power level. (0-100%)
10
Set or read a user defined name. (11 characters)
51
Read the model number of the device.
16
Set or read the interval in milliseconds that a sleeping
device will wake to request a full wake from the base
station. (default 3000)
Select whether to use Carrier Sense Multiple Access
18
techniques on transmission.
Value
0
1
See Unslotted CSMA/CA in Appendix A
69
The voltage measured on the battery.
110
Set or read the battery voltage at which the low
battery flag will be set in all received packets and in
the Status parameter).
75
Defines power save mode.
0 = Awake all the time and transmit at TxInterval.
1 = Sleep. Wake at TXInterval, acquire value, transmit
value, sleep.
76
Time Interval between Transmissions. Set mS
78
Set or read the SampleTime in milliseconds for
acquiring a reading at each TxInterval interval. The
larger the SampleTime the more accurate the reading
but at the expense of battery life. (Default 5)
77
Time period before switching to low power sleep mode
if no StayAwake command or trigger received.
Setting to zero disables.
119
Set or read the 2 byte Data Tag that is used when
transmitting the weight in a Data Provider Packet.
Note that default value is set to last 2 bytes of ID.
Not supported in this
Description
Disabled
The Carrier Sense Multiple Access will be
disabled.
NOT RECOMMENDED
Enabled
The Carrier Sense Multiple Access will be
enabled.
Native
Read /
Data
Write
Type
BINARY 3
R
bytes
FLOAT
R
UINT8
RW
BINARY
RW
16 Bytes
UINT8
RW
STRING
RW
11 Bytes
STRING
R
11 Bytes
UINT16
RW
UINT8
RW
FLOAT
R
FLOAT
RW
UINT8
RW
INT32
RW
UINT16
RW
UINT16
RW
UINT16
RW