Technical Data - Danfoss ERC 211 Installation Manual

Digital controller for refrigeration and defrost, 1 relay
Hide thumbs Also See for ERC 211:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

7 - Technical Data

FEATURES
Power supply
Rated power
Inputs
Allowed sensors types
Sensors included in Kit Solution
Accuracy
Output
| 12
DESCRIPTION
115 V AC / 230 V AC 50/60 Hz, galvanic isolated low voltage regulated
power supply
Less than 0.7 W
2 inputs:
1 analogue, 1 analogue/digital
NTC 5000 Ohm at 25 °C, (Beta value=3980 at 25/100 °C - e.g. EKS 211)
NTC 10000 Ohm at 25 °C, (Beta value=3435 at 25/85 °C - e.g. EKS 221)
PTC 990 Ohm at 25 °C, (e.g. EKS 111)
Pt1000, (e.g. AKS 11, AKS 12, AKS 21)
NTC 10000 Ohm at 25 °C, cable length = 1.,5 m
Measuring range:
-40 – 105 °C (-40 – 221 °F)
Controller accuracy:
+/-1 K below -35 °C, +/- 0.5 K between -35 – 25 °C,
+/-1 K above 25 °C
DO1 Compressor relay:
16 A, 16 (16) A, EN 60730
10 FLA/60 LRA at 230 V, UL60730
16 FLA/72 LRA at 115 V, UL60730
Instruction sheet | ERC 211
DKRCE.PI.RL0.F6.ML

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Erc 214Erc 213

Table of Contents