Quick Configuration At Power Up - Danfoss ERC 211 Installation Manual

Digital controller for refrigeration and defrost, 1 relay
Hide thumbs Also See for ERC 211:
Table of Contents

Advertisement

Available languages
  • EN

Available languages

  • ENGLISH, page 1

3 - Quick Configuration at Power Up

y
STEP 1: Power on
y
STEP 2: Select the quick configuration menu
Within 30 seconds of power on, press "<" BACK for 3 seconds.
The main switch "r12" is automatically set to OFF.
y
STEP 3: Select pre-installed application "o61"
The display automatically shows the application selection parameter "o61".
Press SET to select the pre-installed application.
The display shows the default value (eg. "AP0" flashing).
Choose the application type by pressing UP/DOWN and press SET to confirm.
The controller presets parameter values according to the selected application and does not hide relevant parameters.
Tip: you can easily move from AP0 to AP5, and thus select the simplified list of parameters, by pressing the UP key
(circular list).
App
Description
App 0
None (no preset application)
App 1
Medium temperature (4 – 20 °C), without defrost
App 2
Medium temperature (2 – 6 °C), with timed natural defrost
App 3
Medium temperature (2 – 6 °C), with natural defrost stop on air temperature
App 4
Heating Thermostat (20 – 60 °C)
App 5
None (no preset application) with simplified parameter list
| 6
Instruction sheet | ERC 211
DKRCE.PI.RL0.F6.ML

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Erc 214Erc 213

Table of Contents