LOW PRESSURE CUTOUT (LPCO) CONTROL

(S3300 Only)
FUNCTION
Signals the control board to energize and de-energize
the ice machine when suction pressure rises above or
falls below setpoint.
The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint..
Cut-Out
12 psig ±3
CHECK PROCEDURE
1. Connect manifold gauges at suction and
discharge access valves and verify refrigerant
pressure exceeds LPCO cut-in.
2. Isolate LPCO electrical leads, connect a
multimeter and read resistance.
Open = Replace Switch
Closed = Switch OK
Part Number 80-1479-3 7/10
manuals search engine
Specifications
Cut-In
35 psig ±3