Manitowoc SD0302A Technician's Handbook page 130

S series; s300 series; s420 series; s450 series; s500 series; s850 series; s1000 series; s1200 series; s1400w series; s1400a series; s1400n series; s1800w series; s1800a series; s1800n series
Hide thumbs Also See for SD0302A:
Table of Contents

Advertisement

YES
Is head pressure high &
YES
YES
NO
Is harvest valve energized?
suction pressure low
in harvest?
Replace Harvest Valve
Refer to Sequence of
Operation &
NO
Wiring Diagrams
Is head pressure low &
YES
suction pressure low
in harvest?
Refer to Harvest Pressure
Regulating Valve
NO
Diagnostics
Refer to Symptom #4 -
Will Not Harvest, Freeze
Cycle Normal & Ice Cubes are
YES
Melted Flowchart
Is head pressure normal &
Repeat this flowchart &
NO
suction pressure normal
verify all data
in harvest?
Single Evaporator Systems with Dual Harvest Valves: If one Harvest Vavle is open and the other is restricted / stuck closed you may have
normal harvest pressures. Look for ice not melting on one side of the evaporator.