Manitowoc SD0302A Technician's Handbook page 172

S series; s300 series; s420 series; s450 series; s500 series; s850 series; s1000 series; s1200 series; s1400w series; s1400a series; s1400n series; s1800w series; s1800a series; s1800n series
Hide thumbs Also See for SD0302A:
Table of Contents

Advertisement

Downloaded from
www.Manualslib.com
2. Close the vacuum pump valve, the low side
service valve, and the low side manifold gauge
valve.
3. Open the high side manifold gauge valve, and
backseat the high side service valve.
4. Open the charging cylinder and add the proper
refrigerant charge (shown on nameplate) through
the discharge service valve.
5. Let the system "settle" for 2 to 3 minutes.
6. Place the toggle switch in the ICE position.
7. Close the high side on the manifold gauge set.
Add any remaining vapor charge through the
suction service valve (if necessary).
Manifold gauges must be removed properly to
NOTE:
ensure that no refrigerant contamination or loss
occurs.
8. Make sure that all of the vapor in the charging
hoses is drawn into the ice machine before
disconnecting the charging hoses.
A. Run the ice machine in freeze cycle.
B. Close the high side service valve at the ice
machine.
C. Open the low side service valve at the ice
machine.
D. Open the high and low side valves on the
manifold gauge set. Any refrigerant in the
lines will be pulled into the low side of the
system.
E. Allow the pressures to equalize while the ice
machine is in the freeze cycle.
F. Close the low side service valve at the ice
machine.
G. Remove the hoses from the ice machine and
install the caps.
172
manuals search engine
Part Number 80-1479-3 7/10