LOW PRESSURE CUTOUT (LPCO) CONTROL

FUNCTION
Signals the control board to energize and de-energize
the ice machine when suction pressure rises above or
falls below setpoint.
The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint.
Cut-Out
12 psig ±3
CHECK PROCEDURE
1. Connect manifold gauges at suction and
discharge access valves and verify refrigerant
pressure exceeds LPCO cut-in.
2. Navigate to LPCO input on display
Press the Menu button.
Scroll down to Service and press right arrow.
Scroll down to Diagnostics and press right arrow
Scroll down to Inputs and press right arrow to
display LPCO reading
3. LPCO display indicates
A. Open = Replace Switch
B. Closed = Switch OK
250
Specifications
Part Number Preliminary 6/11
Cut-In
35 psig ±3