YES
Refer to Heavily Scaled
Cleaning Procedure
Downloaded from
www.Manualslib.com
Is the evaporator dirty?
(Dry evaporator first then check)
Discharge line temperature is normal
at the end of the freeze cycle?
S850/S1000 (A/W) = >140F/60C
All other S Models = >150F/65C
Refer to Symptom #2
Freeze Cycle Operational
Analysis Table
manuals search engine
NO
NO
NO
YES
Refer to Manual
Cleaning Procedure