S1600N
All Remote Air-cooled Condenser
Characteristics may vary depending on operating conditions.
CYCLE TIMES
Freeze Time + Harvest Time = Total Cycle Time
Air Temp.
Entering
Condenser
°F/°C
10.4-11.5
-20/-29 to 70/21
10.5-11.5
80/27
10.8-11.9
90/32
11.7-12.8
100/38
10.4-11.5
110/43
1 Times in minutes
24 HOUR ICE PRODUCTION
Air Temp. Entering
Condenser
°F/°C
-20/-29 to 70/21
80/27
90/32
100/38
110/43
1 Based on average ice slab weight of 13 - 14.125 lb.
2 Ratings with JC1395 condenser
OPERATING PRESSURES
Freeze Cycle
Air Temp.
Entering
Discharge
Condenser
Pressure
°F/°C
PSIG
-20/-29 to
220-230
50/10
250-275
70/21
250-290
80/27
255-300
90/32
270-340
100/38
310-370
110/43
1 Suction pressure drops gradually throughout the freeze cycle
Part Number 80-1479-3 7/10
manuals search engine
Freeze Time
Water Temperature °F/°C
50/10
70/21
11.2-12.3
12.4-13.6
11.7-12.8
12.5-13.7
11.7-12.8
13.0-14.3
12.9-14.1
13.8-15.2
11.2-12.3
12.4-13.6
Water Temperature °F/°C
50/10
70/21
1570
1470
1560
1420
1520
1420
1420
1300
1570
1470
Suction
Discharge
Pressure
Pressure
PSIG
PSIG
40-28
100-160
50-28
100-170
50-28
100-175
52-30
100-175
54-31
110-180
56-32
120-190
Harvest
1
Time
90/32
1 - 2.5
12
90/32
1350
1340
1290
1220
1350
Harvest Cycle
Suction
Pressure
1
PSIG
65-85
70-85
70-90
75-95
75-95
80-100
255