LOW PRESSURE CUTOUT (LPCO) CONTROL
FUNCTION
Signals the control board to energize and de-energize
the ice machine when suction pressure rises above or
falls below setpoint.
The LPCO control is closed at pressures above
setpoint and opens at pressures below setpoint.
Cut-Out
12 psig ±3
CHECK PROCEDURE
1. Connect manifold gauges at suction and
discharge access valves and verify refrigerant
pressure exceeds LPCO cut-in.
2. Navigate to LPCO input on display
•
Press the Menu button.
•
Scroll down to Service and press right arrow.
•
Scroll down to Diagnostics and press right arrow
•
Scroll down to Inputs and press right arrow to
display LPCO reading
3. LPCO display indicates
A. Open = Replace Switch
B. Closed = Switch OK
184
Specifications
Part Number STH026 2/12
Cut-In
35 psig ±3