earth (directly buried). For other conditions, size the cables according to local safety regulations,
appropriate input voltage and the load current of the drive.

Output (motor) cable sizes

The table below gives copper and aluminum cable types with concentric copper shield for
nominal current. For drawings of the terminals, see chapter
Note: With no options selected, each inverter module of the drive is to be individually
cabled to the motor. See also sections
(page 50) and
Common output terminal (option +H366)
Drive type
ACS880-37-...
U
= 400 V
N
0450A-3
2 × (3 × 240 + 72 Cu)
0620A-3
4 × (3 × 150 + 41 Cu)
0870A-3
4 × (3 × 240 + 72 Cu)
1110A-3
6 × (3 × 185 + 57 Cu)
1210A-3
6 × (3 × 240 + 72 Cu)
1430A-3
8 × (3 × 185 + 57 Cu)
1700A-3
8 × (3 × 240 + 72 Cu)
2060A-3
9 × (3 × 240 + 72 Cu)
2530A-3
12 × (3 × 240 + 72 Cu)
U
= 500 V
N
0420A-5
2 × (3 × 240 + 72 Cu)
0570A-5
3 × (3 × 185 + 57 Cu)
0780A-5
4 × (3 × 185 + 57 Cu)
1010A-5
6 × (3 × 150 + 41 Cu)
1110A-5
6 × (3 × 185 + 57 Cu)
1530A-5
8 × (3 × 185 + 57 Cu)
1980A-5
9 × (3 × 240 + 72 Cu)
2270A-5
12 × (3 × 185 + 57 Cu)
U
= 690 V
N
0320A-7
2 × (3 × 150 + 41 Cu)
0390A-7
2 × (3 × 185 + 57 Cu)
0580A-7
3 × (3 × 185 + 57 Cu)
0660A-7
4 × (3 × 150 + 41 Cu)
0770A-7
4 × (3 × 185 + 57 Cu)
0950A-7
6 × (3 × 150 + 41 Cu)
1130A-7
6 × (3 × 185 + 57 Cu)
1450A-7
9 × (3 × 150 + 41 Cu)
1680A-7
9 × (3 × 185 + 57 Cu)
1950A-7
9 × (3 × 240 + 72 Cu)
2230A-7
12 × (3 × 185 + 57 Cu)
2770A-7
12 × (3 × 240 + 72 Cu)
12 × (3 × 300 + 88 Cu)
3310A-7
XLPE insulated only
1. The cable sizing is based on max. 9 cables laid on a cable ladder side by side, three ladder type trays one
Common motor terminal cubicle (option +H359)
1)
IEC
Al cable size
2
mm
2 × (3 × 185 + 95)
3 × (3 × 150 + 70)
3 × (3 × 240 + 120)
4 × (3 × 240 + 120)
6 × (3 × 150 + 70)
6 × (3 × 185 + 95)
6 × (3 × 240 + 120)
6 × (3 × 300 + 150)
9 × (3 × 240 + 120)
2 × (3 × 150 + 70)
2 × (3 × 240 + 120)
3 × (3 × 150 + 70)
4 × (3 × 185 + 95)
4 × (3 × 240 + 120)
6 × (3 × 185 + 95)
6 × (3 × 300 + 150)
9 × (3 × 185 + 95)
2 × (3 × 150 + 70)
2 × (3 × 240 + 120)
4 × (3 × 120 + 70)
4 × (3 × 120 + 70)
4 × (3 × 185 + 95)
4 × (3 × 240 + 120)
6 × (3 × 185 + 95)
6 × (3 × 240 + 120)
6 × (3 × 300 + 150)
9 × (3 × 185 + 95)
12 × (3 × 185 + 95)
12 × (3 × 240 + 120)
Guidelines for planning the electrical installation 79
Dimensions
(page 50).
Cu cable size
2
mm
2 × (3 × 95 + 50)
(page 191).
2)
US
Cu cable size
AWG/kcmil
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA
TBA

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs880-17

Table of Contents