External Power Supply For The Control Unit (Xpow) - ABB ACS880-37 Hardware Manual

Hide thumbs Also See for ACS880-37:
Table of Contents

Advertisement

128 Control units of the drive
Notes:
The wire size accepted by all screw terminals (for both stranded and solid wire) is
2
0.5 ... 2.5 mm
(24...12 AWG). The torque is 0.5 N·m (5 lbf·in).
1)
See section
Drive-to-drive link
2)
See chapter
The Safe torque off function
3)
0 = Acceleration/deceleration ramps defined by parameters 23.12/23.13 in use.
1 = Acceleration/deceleration ramps defined by parameters 23.14/23.15 in use.
4)
Constant speed 1 is defined by parameter 22.26.
5)
See section
DIIL input
6)
Total load capacity of these outputs is 4.8 W (200 mA at 24 V) minus the power taken by
DIO1 and DIO2.
7)
Determines whether DICOM is separated from DIOGND (ie. common reference for
digital inputs floats; in practice, selects whether the digital inputs are used in current
sinking or sourcing mode). See also
DICOM = DIOGND ON: DICOM connected to DIOGND. OFF: DICOM and DIOGND
separate.
8)
Current [0(4)...20 mA, R
selected by switch AI1. Change of setting requires reboot of control unit.
9)
Current [0(4)...20 mA, R
selected by switch AI2. Change of setting requires reboot of control unit.

External power supply for the control unit (XPOW)

The BCU-x2 is powered from a 24 V DC, 2 A supply through terminal block XPOW. A
second supply can be connected to the same terminal block for redundancy.
DI6 as a PTC sensor input
PTC sensors can be connected to this input for motor temperature measurement as
follows. The sum of the sensor resistances must not exceed the threshold resistance of
the digital input at normal motor operating temperature. Do not connect both ends of the
cable shield directly to ground. If a capacitor cannot be used at one end, leave that end of
the shield unconnected. See the firmware manual for parameter settings.
Note: PTC sensors can alternatively be connected to FEN-xx encoder interface module.
T
T
T
PTC
WARNING! As the inputs pictured above are not insulated according to
IEC 60664, the connection of the motor temperature sensor requires double or
reinforced insulation between motor live parts and the sensor. If the assembly
does not fulfill the requirement, the I/O board terminals must be protected against contact
(page 129).
(page 223).
(page 129).
Ground isolation diagram
= 100 ohm] or voltage [0(2)...10 V, R
in
= 100 ohm] or voltage [0(2)...10 V, R
in
3.3 nF
> 630 V AC
on page 133.
+24VD
"0" > 4 kohm
DI6
"1" < 1.5 kohm
I
= 5 mA
max
> 200 kohm] input
in
> 200 kohm] input
in