138 Start-up
Action
Safety
WARNING! Obey the safety instructions during the start-up procedure. See chapter
instructions
on page

Checks/Settings with no voltage connected

Ensure that the disconnector of the supply transformer is locked to the off (0) position, ie. no voltage
is, and cannot be connected to the drive inadvertently.
Check that the main switch-disconnector [Q1.1] is switched off, or main breaker [Q1] racked out.
Check that the grounding switch [Q9.1] (option +F259) is switched on.
Check the mechanical and electrical installation of the drive. See
Check the settings of breakers/switches in the auxiliary circuits. See the circuit diagrams delivered
with the drive.
Check the tap settings of transformers T21, T101 (if present) and T111 (if present). See
settings of transformers T21, T101 and T111
Disconnect any unfinished or uninspected auxiliary voltage (115/230 V AC) cables that lead from the
terminal blocks to the outside of the equipment.
Check that both channels of the Safe torque off circuit connected to the STO inputs of both the supply
control unit [A51] and the inverter control unit [A41] are closed. Refer to the wiring diagrams delivered
with the drive.
If the Safe torque off functionality is used, check that the STO OUT output on the inverter control unit
[A41] is chained to the STO inputs of all inverter modules.
If the Safe torque off functionality is not used, check that the STO input on all inverter modules is
correctly wired to +24 V and ground.
Drives with ground fault monitoring for IT (ungrounded) systems (option +Q954): Adjust the settings
of the ground fault monitor to suit the installation. See the circuit diagrams of the delivery and
IRDH275B Ground Fault Monitor Operating Manual by Bender (code: TGH1386en).
Drives with Pt100 relays (option +(n)L506):
• Check the connections against the circuit diagrams of the delivery.
• Set the alarm and trip levels of the Pt100 relays.
Set the alarm and trip levels of the Pt100 relay as low as possible based on the operating
temperature and test results of the machine. The trip level can be set, for example, 10 °C higher than
what the temperature of the machine is at maximal load in the maximum environmental temperature.
We recommend to set the operating temperatures of the relay, typically for example, as follows:
• 120...140 °C when only tripping is in use
• alarm 120...140 °C and trip 130...150 °C when both alarm and tripping are used.
Powering up the auxiliary circuit of the drive
Make sure that it is safe to connect voltage. Ensure that
• nobody is working on the drive or circuits that have been wired from outside into the drive cabinet
• the cover of the motor terminal box is in place.
Drives with a voltmeter (option +G334): Make sure that the circuit breaker of the measuring circuit
[F5.1] is closed.
Close the circuit breakers and/or fuse disconnectors supplying the auxiliary voltage circuits.
Close the cabinet doors.
Close the main breaker of the supply transformer.
17.
(page 90).