126 Control units of the drive
Default I/O diagram of the supply control unit [A51]
The diagram below shows the default I/O connections on the supply control unit [A51], and
describes the use of the signals/connections in the supply unit. Under normal
circumstances, the factory-made wiring should not be changed.
Relay outputs
XRO1: Running (energized = running)
250 V AC / 30 V DC
2 A
XRO2: Fault (-1) (energized = no fault)
250 V AC / 30 V DC
2 A
XRO3: MCB ctrl (energized = main contactor/breaker closed)
250 V AC / 30 V DC
2 A
Reference voltage and analog inputs
10 V DC, R
1...10 kohm
L
-10 V DC, R
1...10 kohm
L
Ground
Not in use
0(2)...10 V, R
> 200 kohm
in
Not in use
0(4)...20 mA, R
= 100 ohm
in
Analog outputs
Not in use
Not in use
Drive-to-drive link
Not in use
Safe torque off
Safe torque off. Both circuits must be closed for the supply unit to start.
(IN1 and IN2 must be connected to OUT.)
Digital inputs
Temperature fault (0 = overtemperature)
Run / enable (1 = run enable)
MCB feedback (1 = main contactor/breaker closed)
Circuit breaker fault (0 = auxiliary circuit breaker or switch open)
Ground (earth) fault (1 = ground fault monitoring tripped)
Reset (0 -> 1 = fault reset)
Emergency stop (0 = emergency stop activated) (units with em. stop option only)
Digital input/outputs
Not in use
Not in use
XRO1...XRO3
NO
3
COM
2
NC
1
NO
3
COM
2
NC
1
NO
3
COM
2
NC
1
XAI
+VREF
1
-VREF
2
AGND
3
AI1+
4
AI1-
5
AI2+
6
AI2-
7
XAO
AO1
1
AGND
2
AO2
3
AGND
4
XD2D
Shield
4
BGND
3
A
2
B
1
XSTO
IN2
4
IN1
3
SGND
2
OUT
1
XDI
DI1
1
DI2
2
DI3
3
DI4
4
DI5
5
DI6
6
DIIL
7
XDIO
DIO1
1
DIO2
2