110 Electrical installation

Connecting the motor cables

Refer to the drawings below.
WARNING! Obey the instructions in chapter
ignore them, injury or death, or damage to the equipment can occur.
1. Do the steps in section
the work.
2. Remove the shroud in front of the output busbars.
3. For 360° grounding of the shield at the cable entry, remove the outer jacket of each
cable where they pass through the cable entry (a).
4. Cut the cable to suitable length and strip the ends of the individual conductors. Twist
the shield strands together to form a separate conductor and wrap it with tape.
5. Crimp suitable lug terminals onto the phase conductors and the ground conductor.
The dimensions of the output busbars are shown in chapter
6. Connect the phase conductors of the motor cable to the U2, V2 and W2 terminals. You
can temporarily remove the plastic insulators (b) between the busbars to make the
connecting work easier.
WARNING! The plastic insulators (b) between the busbars must be in place when
the inverter is powered.
7. Connect the shield (and any grounding conductors) of the cable to the PE busbar
close to the cable entries.
8. Secure the cable mechanically.
9. Repeat the procedure for each motor cable.
10. Refit the shroud removed earlier.
11. At the motor, connect the cables according to instructions from the motor
manufacturer. Pay special attention to the phase order. For minimum radio-frequency
interference, ground the cable shield 360 degrees at the cable entry of the motor
terminal box, or ground the cable by twisting the shield so that the flattened shield is
wider than 1/5 of its length.