Start-Up And Acceptance Test; Checks And Settings With No Voltage Connected; Settings With Voltage Connected; Acceptance Test - ABB ACS880-07 User Manual

Emergency stop, stop category 0 (option +q951)
Hide thumbs Also See for ACS880-07:
Table of Contents

Advertisement

18 Option description and instructions

Start-up and acceptance test

You need the Drive composer PC tool or a control panel to perform the start-up and

acceptance test.

Initial status: Make sure that the drive is ready for use, that is, you have done the tasks of
the drive start-up procedure. See the hardware manual.
Action
WARNING! Obey the
damage to the equipment can occur.

Checks and settings with no voltage connected

If any connections of the emergency stop circuit have been done on site (such as wiring of additional
emergency stop buttons, connection of shipping splits of large drives, etc.), check the connections
against the appropriate circuit diagrams.
Drives with R8i inverter modules: Check that the STO OUT output on the inverter control unit [A41] is
chained to the STO inputs of all inverter modules. The STO circuit is disabled in spare part modules.
Check that the hardware settings relevant to the safety function are set as defined in section
Hardware settings
on page 17.

Settings with voltage connected

Check that the parameters relevant to the safety function are set as defined in section
settings
on page 16.
Acceptance test
Ensure that the motor can be run and stopped freely during the test.
We recommend that you monitor these signals with the Drive composer PC tool:
• 01.01 Motor speed used (rpm)
• 01.02 Motor speed estimated (rpm)
• 01.07 Motor current (A)
• 01.10 Motor torque (%)
• 23.01 Speed ref ramp input (rpm)
• 23.02 Speed ref ramp output (rpm)
• 90.01 Motor speed for control (rpm)
• 90.10 Encoder 1 speed (rpm) (if you use an encoder)
Start the drive and ensure that the motor is running. If possible, use a motor speed close to the
maximum speed of the application.
Push the emergency stop button [S61].
Ensure that the drive stops the motor by coasting and displays a related warning. See section
Emergency stop indications
Ensure that the indication lamp [P62] switches on.
Drives with R8i inverter modules: Make sure that "STO hardware failure" (5090) is not generated.
Ensure that you cannot switch the power on with the operating switch.
Ensure that you cannot start the drive and motor from any control location: Ensure that the motor
does not start even if you switch the start signal off and on or push the start key of the panel.
Turn the emergency stop button [S61] until it releases and returns to the up position.
Safety
instructions, page 7. If you ignore them, injury or death, or
on page 20.