Download Print this page

Gira 2399 02 Operating Instructions Manual page 14

Presence detector and motion detector 360 deg compact
Hide thumbs Also See for 2399 02:

Advertisement

Presence detector and motion detector 360° compact
Saving the current brightness as the switch-on brightness
The Teach function can be used to save the current brightness as a switch-on brightness.
i Do not shade the device during the measuring process.
o
Create the desired lighting situation, e.g. switch light on or off.
o
Press the ũ button for longer than 10 seconds.
The Teach function is activated, the current brightness is saved as the switch-on
brightness and is used after a maximum of 3 minutes.
i If a value greater than 2000 lux is saved, the motion detector switches to day operation
independent of the brightness.
Setting fixed run-on time
o
Press 30 s Ů, 2 min Ů, 5 min Ů or 30 min Ůbutton.
i If the run-on time is shortened, then it only becomes active after the device has switched
off once. To cancel a running run-on time, set the special function Continuous on
for example and then switch back to Automatic operation (see Operation).
Setting individual run-on time
The individual run-on time can be set within a range of 10 seconds to 60 minutes. One of the
fixed run-on times can be set again at any time.
o
Press 0-1 h Ů button.
Run-on time starts.
o
When the required run-on time is reached, press 0-1 h Ů button.
The device saves the run-on time.
i If the run-on time is shortened, then it only becomes active after the device has switched
off once. To cancel a running run-on time, set the special function Continuous on
for example and then switch back to Automatic operation (see Operation).
Setting the dynamic run-on time
The device adapts the run-on time to the motion situation.
o
Press the Dyn. Ů button for longer than 10 seconds.
The dynamic run-on time is activated.
i To switch off the function, press the Reset button for between 4 and 10 seconds
Switching on short time operation
o
Press 1 s Ů button.
i No individual or dynamic run-on time can be set in short time operation.
i To switch off short-time operation, set a fixed or individual run-on time.
Switching on switch-off warning
Switch-off warning is switched off.
o
Press the ŭ button for longer than 10 seconds.
Switch-off warning is switched on. If pressed again, the switch-off warning is switched off
again.
i The function is also switched off if the Reset button is pressed for between 4 and
10 seconds.
Switching on the function as a twilight switch
All the PIR sensors must have been switched off for the device to work as a twilight switch.
o
Press the PIR A, PIR B and PIR C buttons for longer than 10 seconds.
The device works as a twilight switch as soon as the last PIR sensor has been switched
off. The red LED lights up.
i If day operation is set as the switch-on brightness, the light remains off continuously.
i It is not possible to switch via a 2-wire extension or installation button.
82593212
12.01.2017
14/18

Advertisement

loading