Download Print this page

Gira 2399 02 Operating Instructions Manual page 11

Presence detector and motion detector 360 deg compact
Hide thumbs Also See for 2399 02:

Advertisement

Presence detector and motion detector 360° compact
o
Connect the sensor top according to the connection diagram (Figure 9) or switch the
sensor tops according to the circuit diagram (Figure 10).
o
If multiple miniature circuit breakers supply dangerous voltages to the device or load,
couple the miniature circuit breakers or label them with a warning, to ensure disconnection
is guaranteed.
Connection assignment
black, BK, L
brown, BR, ↓
blue, BU, N
grey, GY, 1
PE
o
Optionally, connect the installation button (14) (Figure 9) or (Figure 10). This is only
necessary if manual operation is also desired.
i Lit installation buttons may only be connected if they have an N terminal.
i In the case of single devices, a 2-wire extension can be used as an alternative to the
installation button (14).
o
Screw the sensor top (2) to connection box (1) with screws (10) and mounting pins (9)
(Figure 7).
Limiting the detection area using the push-on cover
The push-on cover can be used to limit the detection area, e.g. in order to mask out interference
sources.
Cover size
Complete push-on cover
Area I cut out
Areas I + II cut out
without push-on cover
o
Pull off push-on cover.
82593212
External conductor
Switched external conductor
Neutral conductor
Installation button connection
Earth conductor
Figure 11: Push-on cover
Range on the ground
(mounting height 3 m)
Ø approx 4.5 m
Ø approx. 7.5 m
Ø approx. 12 m
Ø approx. 20 m
12.01.2017
11/18