Characteristics (cont.)
The table opposite serves as an
example for a parallel-connected
installation comprising up to four UPS
units.
for installations with redundant units,
take into account only the units
required to supply the load power (e.g.
for an installation made up of 3 parallel-
connected UPS units, one being
redundant, only 2 UPS units are used
to determine bypass AC source and
load currents and cable cross-
sections);
this table has been drawn up for
rated phase-to-phase bypass AC
source and load voltages of 400 V and
full rated load with a power factor of
0.8. For voltages of 380 V or 415 V,
multiply the indicated currents by 1.05
and 0.96 respectively, then modify the
cable cross-sections accordingly, if
necessary.
The cable cross-sections in this table
concern the parts illustrated in bold in
the simplified diagram in figure 3,
where:
1: normal AC source,
2: bypass AC source,
A: external bypass.
8 -
E-51028231XU/BH
Parameters for bypass AC source and load cables for a parallel UPS
configuration
Rated unit
Number of
output
parallel-
in kVA
connected
units
20
2
3
4
30
2
3
4
40
2
3
4
50
2
3
4
60
2
3
4
80
2
3
4
100
2
3
4
120
2
3
4
160
2
3
4
200
2
3
4
(1) cable cross-sections are given for copper
conductors of the U1000 R02V type (increase by
30% for aluminium conductors). They are
calculated according to permissible temperature
rise and allow for line voltage drops over a
2
Fig. 3
Total UPS
Bypass AC
rated output
source or load
in kVA
line current
in Amps
40
58
60
87
80
116
60
86
90
129
120
172
80
116
120
174
160
232
100
144
150
216
200
288
120
174
180
261
240
348
160
232
240
348
320
464
200
288
300
432
400
576
240
348
360
522
480
696
320
462
480
693
640
924
400
578
600
866
800
1155
maximum length of 100 m. For greater lengths, the
cross-sections should be chosen to limit voltage
drops to 3%.
A
1
Galaxy 1
2
1
Galaxy 2
2
1
Galaxy 3
2
Cable cross-
section (1)
in mm 2
35
50
50
50
70
70
50
70
120
70
95
150
70
120
185
120
185
2x95
150
185
2x120
185
2x120
2x150
2x95
2x150
3x120
2x120
2x185
3x185