Recommended Protection - MGE UPS Systems Galaxy PW 30 kVA Installation Manual

Galaxy pw series
Table of Contents

Advertisement

Recommended protection

protection upstream of
Galaxy PW
The information provided here is purely
indicative, for a single-UPS unit
supplied by a 380 to 415 V, 50 to 60 Hz
distribution system. Check that all the
criteria mentioned in the previous
section are taken into account (short-
circuit current and protection of the
static-switch semiconductors on the
bypass AC input).
Protection downstream of
Galaxy PW
These protection devices ensure
discrimination for each of the Galaxy
PW output circuits. If the recommended
downstream protection is not installed
and a short-circuit occurs, the result
may be a break longer than 20 ms on
all the other output circuits.
Electrical parameters for determining cable cross-sections
this table has been drawn up for
rated phase-to-phase AC source and
load voltages of 400 V. For voltages of
380 V or 415 V, multiply the currents for
the bypass AC source and the load by
1.05 and 0.96 respectively;
Parameters for cables for a single-UPS unit
Rated UPS
Line currents absorbed in Amps
output
Normal AC source
in kVA
with or
without battery (1)
20
33
30
49
40
66
50
83
60
100
80
133
100
166
120
199
160
262
200
329
(1) The rated normal AC source currents (In) have
been determined for a minimum float charging
voltage of 423 V and full rated load with a power
factor of 0.8.
Ratings of recommended protection devices upstream of a single-UPS unit
(Merlin Gerin circuit breakers)
Rated UPS
Circuit breaker on normal
output
AC input
in kVA
Circuit breaker
20
NS 100N 3P
30
NS 100N 3P
40
NS 100N 3P
50
NS 100N 3P
60
NS 125E 3P
80
NS 160N 3P
100
NS 250N 3P
120
NS 250N 3P
160
NS 400N 3P
200
NS 400N 3P
Ratings of recommended protection devices downstream of a single-UPS unit
(Merlin Gerin circuit breakers)
Rated UPS
Downstream circuit
output
breaker(s)
in kVA
Circuit breaker Control unit
20 to 40 kVA
C60N
50 to 60 kVA
C60N
80 to 120 kVA
C60N
NC100
160 to 200 kVA
NC100
the current values and cable cross-
sections for the normal AC source are
given for full rated load with a power
factor of 0.8 and a battery consuming
its minimum float charging voltage.
the battery current values and cable
cross-sections have been determined
for a battery at the end of discharging;
400 V
Battery
bypass AC
source and load
29
52
43
72
58
103
72
128
87
154
116
205
144
256
174
308
231
410
289
512
(2) the cable cross-sections are given for copper
conductors (increase by 30% for aluminium
conductors). They are calculated according to
permissible temperature rise and allow for line
voltage drops over a maximum length of 100 m
(AC circuits) or 25 m (DC circuits if cables not
Characteristics (cont.)
Circuit breaker on bypass
AC input
Control unit
Circuit breaker
TM 63D
NS 100N 4P
TM 63D
NS 100N 4P
TM 80D
NS 100N 4P
TM 100D
NS 100N 4P
TM 125D
NS 125E 4P
TM 160D
NS 160N 4P
TM 200D
NS 250N 4P
TM 250D
NS 250N 4P
STR 23 SE
NS 400N 4P
STR 23 SE
NS 400N 4P
C 10A
B 20A
C 20A
B 32A
C 50A
B 63A
C 63A
B 100A
the current values and cable sections
for the bypass AC source and load are
given for full rated load with a power
factor of 0.8.
For frequency converters, the
parameters concerning the bypass AC
source are not applicable.
Cross-sectional area of Cu cables in mm
Normal AC source
400 V
with or without battery
bypass AC
source and load
16
16
25
25
35
35
50
35
50
50
95 or 2x50
70
95 or 2x50
70
95 or 2x50
70
95
95
120
120
provided). For greater lengths, the cross-sections
should be chosen to limit voltage drops to 3% (AC)
or 1% (DC).
Control unit
TM 63D
TM 63D
TM 80D
TM 100D
TM 125D
TM 160D
TM 200D
TM 250D
STR 23 SE
STR 23 SE
2
(2)
Battery
16
25
35
50
70
95 or 2x50
2x70
2x70
2x95
2x95
- 7
E-51028231XU/BH