SPECIFICATIONS
Table 12. Power Connections
Model
U Models
EU Models
Table 13. Environmental and Safety
Operating Temperature
Storage Temperature
Relative Humidity
Operating Altitude
Audible Noise
Surge Suppression
Safety Conformance
Agency Markings
EMC (Class A)
Table 14. Battery
UPS Configuration
EBM Configuration
Type
Table 15. Battery Runtimes
UPS
UPS Internal Batteries
5000 VA
6000 VA
NOTE Battery times are approximate and vary depending on the load configuration and battery charge.
66
EATON Powerware
www.powerware.com
Input Connection
10 ft, L6−30P power cord
Hardwired
U Models
Up to 1,000 meters above sea level
Less than 46 dBA Normal mode, typical load and Battery mode
ANSI C62.41 Category B, IEC 61000−4−5
UL 1778;
CSA C22.2, No. 107.1;
NOM−019−SCFI
cUL, NOM
FCC Part 15
(15) 12V, 5.5 Ah internal batteries
(2 strings of 15) 12V, 5.5 Ah internal batteries
Sealed, maintenance-free, lead-acid
+1 EBM
5 min
22 min
4 min
17 min
®
9135 Two−in−One UPS (5000/6000 VA) User's Guide
(8) 10A, IEC 320−C13; (2) 16A, IEC 320−C19
0°C to 40°C (32°F to 104°F)
−25°C to 40°C (−13°F to 104°F)
5–95% noncondensing
CSA C22.2, No. 107.1;
EN 62040−1−1, IEC 60950−1, IEC 50091−1−1
TUV(GS), CE, cUL, C−tick
EN 62040−2 C1, AS 62040−2 C1, FCC Part 15
+2 EBMs
41 min
33 min
S
164201726 Rev 1
Output Receptacles
(4) NEMA L6−30R
Hardwired with
EU Models
UL 1778;
+3 EBMs
+4 EBMs
1 hr 2 min
1 hr 23 min
50 min
1 hr 7 min