Eaton Powerware 9135 Two-in-One UPS 5000/6000 VA User Manual page 59

Two-in-one ups 5000/6000 va
Table of Contents

Advertisement

Table 4. Output Settings
Function
Factory Setting
Output Voltage
EU Models: 230V
U Models: 208V
Freq Converter
Disable
Output Frequency
EU Models: 50 Hz
U Models: 60 Hz
Eco Mode
Disable
Slew Rate
1 Hz / sec
Bypass Transfer
Yes
If bypass Ac nok?
Interrupt Time
10 ms
Overload Prealarm
105%
Table 5. ON/OFF Settings
Function
Factory Setting
Cold Start
Disable
Forced Reboot
Enable
Auto Restart
Enable
Energy Saving
Disable
Sleep Mode
Enable
Remote Command
Enable
EATON Powerware
Options
200V / 208V / 220V /
240V / 250V
Enable
60 Hz
Enable
0.5 Hz / sec
No
20 ms, ...... , 200 ms
40%, 50%, 70%
Options
Enable
Disable
Enable
Disable
Disable
®
9135 Two−in−One UPS (5000/6000 VA) User's Guide
OPERATION
Comments
User selectable under
frequency−converter mode
See page 50
Transfer to bypass if utility power is
out of tolerance
Break time calibration during load
transfer on utility power out of
tolerance
Alarm if threshold is overrun
Comments
Start on battery
Enables automatic restart of the
system even if utility power is
restored before the end of the
shutdown sequence
UPS restarts automatically when
utility power is restored
Automatic shutdown on battery if
output load level <10%
Enables consideration of shutdown or
restart orders from software to be
authorized
S
164201726 Rev 1
www.powerware.com