The Remote EPO control arrives as shown in Figure 6. See Drawing
164201261---7 in Appendix A for enclosure dimensions, side views, and
knockout patterns.
to UPS
To install a Remote EPO control:
1.
Securely mount the Remote EPO station. Recommended locations include
operator's consoles or exit doors.
2.
Install wiring from the Remote EPO station using ½-in. conduit through the
-in. knockout in either the top or bottom of the UPS.
7/8
3.
Connect the Remote EPO wiring as shown in Tables A and B:
From REPO Station(s)
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio
164201261 Rev. F 111503
Installing a Remote EPO Control
to other equipment
Figure 6. Remote EPO Control
Table A. Remote EPO Wire Terminations
To Communications
TB1---4
TB1---5
UNINTERRUPTIBLE POWER SYSTEM
EMERGENCY OFF
Panel in UPS
TB2---1
Twisted wires (2)
Twisted wires (2)
TB2---2
Remarks
14---18 gauge
n
21