Page 2
Operation of this equipment in a residential area is likely to cause harmful interference in which case the user will be required to correct the interference at their own expense. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation ---------------------------------- SAVE THESE INSTRUCTIONS Conserver Ces Instructions concernant la sécurité.
Installing a Remote Monitor Panel Installing a Relay Interface Module Installing a Supervisory Contact Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Table of Contents ..........
Page 4
Using the Menu Options Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation ..........
Page 5
Printing Selected Information Entire Log (Ctrl + P) Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 ........
Page 7
Figure 23. UPS Monitor Panel Figure 24. Parts of the LCD Screen (Typical for Powerware BPIII HE 75 480/480V Unit) Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 List of Figures ..... .
Page 8
Figure 45. System Meters Figure 46. Battery Test Log Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation viii ......
Powerware BPIII online power protection can be utilized to prevent loss of valuable electronic information, minimize equipment downtime, and/or minimize the adverse effect on equipment production due to unexpected power problems. The Powerware BPIII Harsh Environment (HE) Uninterruptible Power Supply (UPS) system continually monitors incoming electrical power and removes the surges, spikes, sags, and other irregularities that are inherent in commercial utility power.
Using This Manual This manual describes the Powerware BPIII HE UPS installation, operation and routine maintenance. The information in this manual is divided into the sections and chapters listed. Introduction The Introduction provides a brief description of the UPS system, a description of the content of each chapter, safety, text conventions used in the manual and reference information.
The rectifier and inverter are internal UPS components that are together referred to as the power processing unit (PPU) of the UPS. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
If you need to schedule initial startup, need regional locations and telephone numbers, have a question about any of the information in this manual, or have a question this manual does not answer, please call Powerware at: United States Canada Outside the U.S.
Page 14
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Cabinet and outlets are on the top of the UPS cabinet. You must allow clearance in front of and above each cabinet for proper air circulation. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Carefully inspect the outer packaging for evidence of damage during transit. CAUTION: Do not install a damaged cabinet. Report any damage to the carrier and contact your local sales or service office immediately. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation OUTER PACKAGING FOAM CUSHION...
After the foam cushions clear the floor, remove the hardware loosened in step 3. Pull the foam cushions out from under the cabinet, and discard or recycle them in a responsible manner. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 in.) above the floor...
For external wiring requirements, including the minimum AWG size of external wiring, see Tables A and E of Appendix A. The power wiring for this equipment is rated at 90˚C. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation FRONT SUPPORT...
Environmental cabinets assembled. The top view shows the cable entry plate in the Environmental cabinet. TOP VIEW FRONT VIEW Figure 4. UPS and Environmental Cabinets Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 UPS System...
Use the holes provide in the cabinet sides. Attach a ground to the joined cabinets using the procedure “Grounding Joined Cabinets” in this chapter. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Environmental cabinet through the cutout in cabinet sides. Connect connectors P20, P22, and P23 to connectors J20, J22, and J23 respectively. Reinstall UPS Cabinet sheetmetal shield. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Startup and operational checks should be performed only by authorized service personnel. Contact service in advance (usually a two week notice is required) to reserve a preferred startup date. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Installation Checklist to be sure you have completed all applicable equipment installation. NOTE: The Installation Checklist MUST be completed prior to starting the UPS system for the first time. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Adequate workspace exists around the UPS and other cabinets. Adequate lighting is provided around all UPS equipment. A 120V service outlet is located within 25 feet of the UPS equipment. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 28
Notes Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Connect the Remote EPO wiring as shown in Tables A and B: Table A. Remote EPO Wire Terminations From REPO Station(s) TB1---4 TB1---5 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 UNINTERRUPTIBLE POWER SYSTEM to other equipment Figure 6. Remote EPO Control...
Page 30
Table B. Remote EPO switch wiring must be in accordance with UL Class II requirements. Secure the UPS by reversing all steps taken to prepare it for Remote EPO installation. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Table B. Remote EPO TWISTED WIRES (2)
Table C. Optional Monitoring Accessories Number and Type of Accessories Permitted Remote Monitor Panel — — — Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Relay Interface Panel Supervisory Contact Module — — —...
Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation FLUSH MOUNT Figure 7. Remote Monitor Panel (RMP) SURFACE MOUNT (FOR HANGING) WIRES MUST BE TWISTED 164291261 Rev. F 111503...
TB1---7 From RMP B (if used) TB1---4 TB1---5 TB1---6 TB1---7 Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation DB---9 CONNECTOR (ON COMMUNICATIONS PANEL OF THE UPS) TB1 TB2 Figure 9. Wiring an RMP to the UPS Table D. RMP Wire Terminations...
Page 35
6, respectively; otherwise, secure the UPS cabinet by reversing the steps contained in procedure “To Prepare the UPS for Wiring to an RMP , RIM, SCM, or Remote EPO” of Chapter 2. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 36
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Figure 10 shows the RIM with its four 15-pin connectors labeled J1 through J4. Drawing 164201261---8 in Appendix A outlines the enclosure dimensions. 15-PIN D-SUB CONNECTORS Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 FLUSH MOUNT Relay Interface Module Figure 10.
Figure 12). Use two screws from the spare parts kit to secure the terminal block bracket to the Communications Panel. Connect to Port 1 (DB---9) on Communications Panel Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Figure 11. Terminal Block Bracket in. knockout in 7/8- FUSE...
DB---9 CONNECTOR (ON COMMUNICATIONS PANEL OF THE UPS) TB1 TB2 Figure 12. Wiring an RIM to the UPS Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 40
From RIM A TB1---4 TB1---5 TB1---6 TB1---7 From RIM B (if used) TB1---4 TB1---5 TB1---6 TB1---7 Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Table E. RIM Wire Terminations To UPS TB3---1 TB3---2 TB3---3 TB3---4 To UPS TB3---5 TB3---6...
(RMPs, RIMs, or SCMs) can be installed. Refer to Chapter 4, Table C for the number of accessories permitted. See Drawing 164201261---9 in Appendix A for enclosure dimensions, side views, and knockout patterns. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Installing a Supervisory Figure 13.
Figure 15). Use two screws from the spare parts kit to secure the terminal block bracket to the Communications Panel. Connect to Port 1 (DB---9) on Communications Panel Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Figure 14. Terminal Block Bracket in. knockout in 7/8- FUSE...
TB1---7 From SCM B (if used) TB1---4 TB1---5 TB1---6 TB1---7 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 DB---9 CONNECTOR (ON COMMUNICATIONS PANEL OF THE UPS) TB1 TB2 Figure 15. Wiring an SCM to the UPS...
Note: Supervisory contacts are rated at 2.0 amps at 28 Vdc or 120 Vac and 0.15 amp at 115 Vdc. Supervisory contacts require external power supply. Internal 24 Vdc is not capable of supplying contact current. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Figure 16. Supervisory Contact Module TB2 164291261 Rev. F 111503...
An alarm is a system event that requires immediate operator intervention. System events, alarm horns, and indicator lights are described in Chapter 12 --- Responding to System Events. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Understanding UPS Operation...
Looking Inside the UPS The Powerware BPIII HE is a continuous duty, solid-state UPS that supports the following equipment: process control, data processing, and telecommunications/PBX. The Powerware BPIII HE maintains power to the critical loads during commercial electrical power brownout, blackout, overvoltage, undervoltage, and out-of-tolerance frequency conditions.
If the UPS suffers an internal failure, it switches automatically to Bypass mode and remains in that mode until the failure is corrected and the UPS is back in service. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Bypass mode is a normal operating mode, and not an alarm condition. However, if the UPS is unable to return to Normal mode following an automatic transfer to Bypass mode, an alarm condition will be recorded. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation BYPASS INVERTER...
Normal mode and alarm indications clear. However, the process of returning to Normal mode is not instantaneous. The rectifier gradually draws increasing power from the incoming utility until Normal mode is achieved. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 BYPASS...
This breaker is opened to isolate the UPS bypass after the load is transferred to maintenance bypass. The MBP and MIS breakers are electrically interlocked to limit the possibility of UPS system damage from improper operation. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation BYPASS INVERTER (closed)
These control power to and from the UPS, and allow you to change the UPS mode manually. The Control Panel is discussed in Chapter 10. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 54
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
The filter also reduces input harmonic current distortion and minimizes upstream interference that can damage sensitive hardware components. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Controls and Features...
Customer Convenience Outlet An uninterruptible 120 VAC, 0.2 amp, fuse-protected convenience outlet is provided with the optional modem. It is located adjacent to the Communications Panel. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Observe all DANGER, CAUTION, and WARNING notices affixed to the inside and outside of the equipment. • Always conform to the more detailed safety precautions described in “Important Safety Instructions” section of Chapter 15. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Stop and refer to the Operator’s Manual for more information. RISK OF ELECTRIC SHOCK There is a risk of electric shock present, and you should observe associated warnings. The UPS contains high voltages. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
UPS operation. The Monitor Panel is a black rectangular area on the front of the UPS (see Figure 23). UNINTERRUPTIBLE POWER SYSTEM Figure 23. UPS Monitor Panel Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Meters Events Statistics Graphics Figure 24. Parts of the LCD Screen (Typical for Powerware BPIII HE 75 480/480V Unit) The UPS status area contains three lines that display the current state of the UPS. The first line shows the present operational mode of the UPS. The second line shows the highest level of the current active alarms, and the third line shows any notices the UPS has posted.
Use the pushbuttons to adjust the contrast on the LCD screen. Hold down the pushbutton, then press the pushbutton to decrease the contrast. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 pushbuttons to move through the menu titles on the...
If any indicator does not light, its LED may need to be replaced. Contact Customer Service if you have a problem with the indicator lamps. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation pushbuttons simultaneously. The Alarm indicator may be lit pushbuttons pushbuttons 164291261 Rev.
Meters Events Statistics Graphics Figure 25. System Meters Screen (Typical for Powerware BPIII HE 75 480/480V Unit) The Input area shows the phase-to-phase voltage, frequency, and phase current of the incoming utility, followed by the KVA, KW, and power factor measurements. The output area shows the same information for the power being output by the UPS.
When the scroll bar is in the information area, you can press the to scroll through the Event History log. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Uninterruptible Power System...
Battery Minutes 001.3 Events History Active Meters Events Statistics Graphics Setup Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Uninterruptible Power System Shutdown Imminent Active System Events NOTICE: Input power unavailable NOTICE: Bypass Not Available ALARM: Shutdown Imminent Figure 28.
UPS logic has been functioning since the start date. The lower right column shows the percent of availability of the UPS and the bypass source. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Mimic Meters Events Statistics The Mimic screen shows the internal components of the UPS cabinet. The flow of current through the components is highlighted. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Uninterruptible Power System Bypass Rectifier Inverter...
(make it a higher value), press the (make it a lower value), press the upon exit from this screen, be sure the SAVE field is set to YES. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Uninterruptible Power System Set Time &...
SAVE field is set to YES. The setup screens for Port 1 and Port 2 are identical. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Uninterruptible Power System Setup Serial Port 1...
DC to DC converter if the converter shuts down during normal operation. • The PUSH TO RESET pushbutton is described in the “Resetting UPS System after Emergency Power Off” section of this chapter. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation NORMAL PUSH TO RESET BATTERY...
Page 73
UPS internal bypass circuit. This breaker is opened to isolate the UPS bypass after the load is transferred to maintenance bypass. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
CB2 breaker switch to OFF. Then move the CB1 breaker switch to OFF. The bypass source supplies the critical load and the power processor de-energizes. The Bypass mode indicator illuminates on the Monitor Panel. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Open MBP circuit breaker. The critical load is now on UPS bypass. To transfer the critical load to normal mode follow the procedure “To Place the UPS in Normal Mode” at the beginning of this section. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
The DC walks up to 540 VDC. The inverter starts. K3 closes. All fans and blowers are functional. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Horn sounds every 2 seconds. Load Off Converter Offline Bypass AC Under Voltage...
Turn BATTERY switch to OFF. Wait at least four seconds. Turn BATTERY switch to NORMAL. The converter restarts. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 System Normal, On Battery On Battery more than 30 Seconds...
TRIPPED position. The UPS system is now reset. To restart the UPS system, follow the procedure at the beginning of this chapter. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Building Alarm 2, Building Alarm 3, etc., on the LCD screen of the Monitor Panel. You should use twisted pair wires for each alarm input and common. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
UPS is located in a remote area where the UPS alarm horn may not be heard immediately. CAUTION: Contacts should not be operated in excess of 30 VAC or 42.4V peak AC or DC @ 1A maximum. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation ALARM NO ALARM NC COMMON NOTICE NO...
Table 1. Optional Monitoring Accessories Number and Type of Accessories Permitted Remote Monitor Panel — — — Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Figure 37. Remote Monitor Panel Relay Interface Module Supervisory Contact Module —...
Page 82
The UPS is preparing to shut down because the UPS is in Battery mode and the DC voltage is approaching its low limit. This light is accompanied by an audible alarm horn. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
UPS OFF LINE • UTILITY FAILURE • BATTERY WEAK Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Figure 38. Relay Interface Module (pins 1 and 12) Contacts are closed when the UPS is offline.
For descriptions of the status indicators, see “Reading the Status Indicators” section of Chapter 9, “Using the Monitor Panel”. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Responding to System Events...
Check Unit Setup Bypass Contactor (K4) Fail Battery Ground Fault 100% Overload Shutdown 125% Overload Shutdown Over Temperature Shutdown Network Sync Failure Inverter Calibration Required Inverter Setup Required Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Page 87
Check Parallel Setup Parallel System Overload On Battery more than 30 Seconds Check UPM Breaker (CBS) AUX Check Bypass Breaker (CBP) AUX Monitor Calibration Required Monitor Setup Required Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 88
Battery DC Under Voltage Battery Disconnected Battery Not Charged Phase A Current Limit Phase B Current Limit Phase C Current Limit Battery Voltage Low Inv. Logic Power Failure Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Page 89
Input Transient DC Voltage Low DC Voltage High Equalizing Battery Testing Battery Battery Test Failed Input/Battery Current Limit Reduced Input Current Limit Rct. Logic Power Failure Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 90
Building Alarm 6 Active Testing Battery Battery Test Aborted (load) Battery Test Aborted (utility) Battery Passed Test ##Printing Sampled Data Other UPS Bypass Not Available Loss of Redundancy Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Page 91
CONVERTER NOTICES Converter Shutdown Converter In Startup OK To Close CB2 Converter Logic Power OK CONVERTER STATUSES Converter Normal Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 92
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
The following sections describe the serial communications feature, and provide information about connecting hardware, setting up the ports, changing settings, and changing modes. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Serial Communications This chapter describes the serial communications feature of...
Connection COMMUNICATIONS PANEL PORT 2 (DB---25F) RS---232 Connection (Optional) Figure 40. Location of Communications Ports on the Powerware BPIII HE UPS (shown without the Environmental Cabinet) Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Table 3 describes them. Table 2. Pin Assignments for Port 1 (DB---9) Pin # Symbol +24V 485+ 485--- Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 PORT 1 (DB- -9) +24V NOT USED RS232 TXD 485 +...
To save the settings upon exit from this screen, be sure the Save field is set to YES. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
300 baud is not recommended for any mode except Remote Monitor. You can select a baud rate of 300, 1200, 2400, 4800, 9600, or 19,200. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Options Terminal Mode...
Each communications port on the UPS operates in one of five modes which you select when configuring the port using the Setup Port screen. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 300 baud...
Prints all system information Ctrl+B Prints Battery Test Log To use a key combination, hold down the Control key and press the letter key. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation :::: Description Month (3 letters) Day (2 digits)
16:42:05.5 16:42:46.8 16:43:15.8 16:43:42.4 16:44:29.1 12 16:44:36.6 STATUS: JUN 04 12:16:35.9 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Uninterruptible Power System None Event History Log Event Description COMMAND: Keyswitch On STATUS: Auto Mode...
This key sequence prints a listing of all available serial data. This printout contains the information shown on the Event History Log and Meters screens of the UPS (both Figures 44 and 45). Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Uninterruptible Power System Input...
Aborted (Load), or Battery Test Aborted (Utility). If the test ran to completion, Battery Passed Test will appear in the UPS Event History Log. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 UPS # 1...
If 1 is entered at the prompt, you can program the building alarm functions: Program Building Alarms 1. Enable/Disable Default Functions 2. Customize Alarm Messages 3. Return to Main Menu Enter Selection: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
The line following the Enabled Building Alarm Number(s) label indicates which building alarms are currently enabled. (In this example, Building Alarms 1 and 4 are enabled.) Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
If the user wants to center the text portion of the name, the appropriate number of leading spaces should be included when entered. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
NOTE: Password must be six characters in length. <CR> to return with no change. The password will be changed if the user enters and verifies the password. The entry must be six characters. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
No Battery Test Scheduled Enter <CR> to return to Battery Test Setup Menu NOTE: The unit will only perform one battery test in any 24 hour period. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
For a list of products available, contact your sales representative. Remote Monitor Mode This mode provides the interface for the RMP , RIM, or SCM described earlier. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Page 110
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
UPS to call a paging service and send numeric messages. The Housekeeping function maintains the link between the UPS and modem. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Optional Remote Notification...
Remote and local ability to clear Call Out alarms and events. • Error detection and correction for misconfigured and disconnected modems. • Uses standard modems and cables available at your local computer supply center. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
(phone numbers) required. The command sent to the modem for group one is “ATDTS0” and “ATDTS1” for group two. This allows the user to program the phone numbers into the modem. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
UPS logs a modem failure event into the event log. When the modem link is confirmed, the UPS communications resume normal operation and Call Out is enabled. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
An alternative to purchasing a cable is to build your own serial cable using the following pin out description: Male DB25 pin 7 pin 2 pin 3 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Male DB25 pin 7 pin 2 pin 2...
The modem should be a plug and play type. All setup is configured by the UPS. Only the initial phone number needs to be entered by the user. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
NOTE: To set up a group one or group two pager number, refer to “Configuring the Modem to Call a Numeric Pager” section of this chapter. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
NOTE: To set up a group one or group two number to call a computer, refer to “Configuring the Modem to Call a Remote Computer” section of this chapter. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Keying in the “#”...
The final step in configuring the PC modem for use with the UPS is to turn off the echo feature of the modem. This procedure is performed automatically by the UPS. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503...
Chapter 13, “Serial Communications”). If using a standard serial cable, a null modem adapter is required for the connection to the modem. The Powerware BP III HE UPS can only use optional serial Port 2, DB---25F, for the Remote Notification option. This connection is located in the serial communications panel at the base of the UPS cabinet, behind the front door.
Failed Bypass Control Failed Bypass Phase Rotation Go To Bypass Active Battery Contactor (K2) Failed Battery Ground Fault Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Group Group INVERTER MESSAGES -- NOTICES Inv. Logic Power Failed...
Page 122
Rectifier DC Over Voltage Rectifier DC Under Voltage Rectifier Failure Rectifier Setup Required Temperature Sensor Failure Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation RECTIFIER Group Group MESSAGES -- NOTICES Battery Test Failed DC Voltage High DC Voltage Low...
Page 123
Load Over 100% Load Over 125% Monitor Calibration Required Monitor Setup Required Overload Warning Power Supply Failure Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 MONITOR Group Group MESSAGES -- NOTICES Battery Passed Test...
Page 124
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Battery maintenance or battery replacement should be performed by authorized service personnel only. Keep unauthorized personnel away from battery room. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Maintaining the UPS System The components inside the UPS cabinet are secured to a...
ASHRAE rating of 52.2. An AmAir 62 Plus meet these requirements. To remove filters: Loosen captive screw at left side of filter grill. Open grill. Remove and replace filter. Close filter grill and secure with captive screw. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Maintenance Training A basic training course, available from Powerware, gives you a competent working knowledge of UPS operation and teaches you how to perform first level corrective maintenance. For more information about training and other services, contact the Powerware Training Coordinator in Raleigh, North Carolina, or call Powerware field service at 1 -- 800 -- 843 -- 9433.
Page 128
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
Current Input Current Harmonic Content Power Walk-In Power Factor Line Surges Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Product Specifications The following sections detail the input, output and Models 50 kVA, 40kW 62.5 kVA, 50kW...
Synchronous to Bypass Frequency Slew Rate Overload Capability Maximum Output Capability Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 135% + 6 Kw Ripple voltage less than 0.5% peak to peak 100% current at 0.8 power factor 1% (10% to 100% load)
Float Charging Initialize Charge Battery Charge Current Limit Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 0 to 50˚C without derating. However, operating at or near 50˚C will adversely affect battery life (refer to your battery specifications for more information).
Page 132
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 164291261 Rev. F 111503...
164201261---7 • 164201261---8 • 164201261---9 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 The information in this appendix will help you plan for and install Installation Notes Typical UPS System Oneline Drawings of UPS System...
Page 134
Table A. Powerware BPIII HE 50---75 kVA (208, 480, and 600 Volt) Ratings Basic unit rating at 0.8 lagging PF load gg g AC Input to UPS Rectifier Full Load Full Load + Batt. Chg.(max) (.95min.PF) 3 , (1) gnd Minimum conductor size (number per )
Page 135
Non-linear loads can create neutral currents that are greater than 100%. This product can accommodate double-sized neutral terminations if needed. NOTE: Callout letter map to drawing #164201261---3 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 OUTPUT Ratings & External Wiring Requirements for Units...
Page 136
Callout letter map to drawing #164201261---3 A ---4 Ratings & External Wiring Requirements for Ratings DESCRIPTION: DRAWING NO: REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Rating Units 50 Hz 62.5 INPUT/OUTPUT VOLTAGE Amps (max) AWG or...
Page 137
AC Output to Environmental e tal Cabinet Cabinet DC Input from Environmental Environmental Cabinet Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Cable Size of Function Termination Number Phase ‘A’ 1 --- 1 bolt mounting Phase ‘B’...
Page 138
Air Conditioning or Ventilation Heat Rejection BTU/hr (Kg---cal/hr) 23,000 (5796) DESCRIPTION: INSTALLATION NOTES DRAWING NO: REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Tightening Int Hex Torque Size N ---M (lb ---in ) (In.) 42.4 (375) 42.4 (375) 42.4 (375)
Page 139
Table H. Maximum Output Circuit Breaker Ratings Balanced Power System Balanced Power System Balanced Power 75 Balanced Power 62.5 Balanced Power 50 Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Input Voltage Rating 208V 400V 480V...
Page 140
A ---8 Weight Kg (lb) 1878 (4140) DESCRIPTION: INSTALLATION NOTES DRAWING NO: 164201261---1 REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation All Voltage Ratings Point Loading Kg (lb) 8 at 235 (518) SHEET: 7 of 11 DATE: 011500...
Page 141
Not all building alarms are available for customer use. For remote EPO, use an isolated normally open contactor switch (24VDC, 20ma minimum) connected at TB2-1 and TB2-2. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Communications Panel...
Page 142
Contacts used to indicate UPS Battery Contactor is closed. General purpose NO and NC relay contacts. General purpose NO and NC relay contacts. DESCRIPTION: DRAWING NO: REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Description INSTALLATION NOTES SHEET: 164201261---1 DATE: 053099 164291261 Rev.
Page 143
Refer to Tables L, M, and N, and to applicable chapters for information about installing control wiring for options and accessories. Terminal CONTACT RATING: Maximum Switched Voltage Maximum Carrying Current Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Table L. Control Wiring Terminations Description Terminal Function Terminal Block...
Page 144
NOTE: This switch must be a dedicated switch not tied into any other circuits. DESCRIPTION: INSTALLATION NOTES DRAWING NO: REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation SHEET: 164201261---1 11 of 11 DATE: 053099 164291261 Rev. F 111503...
Page 145
UPS CABINET Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 ENVIRONMENTAL CABINET DESCRIPTION: TYPICAL UPS SYSTEM DRAWING NO: REVISION: SHEET: 164201261---2 DATE: 053099 1 of 1 A ---13...
Page 146
UPS SYSTEM WITH 480/480 OR 400/400 VOLT INPUT/OUTPUT DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM DRAWING NO: SHEET: 164201261---3 1 of 4 REVISION: DATE: 053099 Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation A ---14 164291261 Rev. F 111503...
Page 147
UPS SYSTEM WITH 480/208 VOLT INPUT/OUTPUT Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM DRAWING NO: 164201261---3 REVISION: DATE: SHEET: 2 of 4 053099 A ---15...
Page 148
UPS SYSTEM WITH 208/208 VOLT INPUT/OUTPUT DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM DRAWING NO: SHEET: 164201261---3 3 of 4 REVISION: DATE: 053099 Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation A ---16 164291261 Rev. F 111503...
Page 149
UPS SYSTEM WITH 600/208 VOLT INPUT/OUTPUT Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 DESCRIPTION: ONELINE DRAWINGS OF UPS SYSTEM DRAWING NO: 164201261---3 REVISION: DATE: SHEET: 4 of 4 053099 A ---17...
Input Switch (MIS) Source ENVIRONMENTAL CABINET EXTERNAL WIRING DESCRIPTION: LOCATION OF UPS POWER TERMINALS DRAWING NO: REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation Output Critical Load AC Input To UPS Rectifier Neutral Rectifier Input Breaker (CB1)
Page 151
Jumper NOTE: Connections shown are between the UPS cabinet and Environmental cabinet. External connections are shown on sheet 1. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 Ground INTERCABINET WIRING DESCRIPTION: DRAWING NO: REVISION:...
Page 152
DESCRIPTION: UPS CABINET DRAWING NO: SHEET: 164201261---5 1 of 1 Dimensions are in millimeters (inches) REVISION: DATE: 053099 Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation A ---20 164291261 Rev. F 111503...
Page 153
115.8 (4.56) 114.3 (4.50) TO UPS Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 (0.47) TO OTHER Dimensions are in millimeters (inches) EQUIPMENT DESCRIPTION: DRAWING NO: REVISION: 11.9 88.9 (3.50) (3.75) SQUARE Knockout pattern typ.
Page 155
28.6 (1.12) 41.1 (1.62) 190.5 88.9 (7.50) (3.50) EXISTING INTERNAL WIRING Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 215.9 (8.5) 196.8 (7.75) 19.0 Relay Interface Module CONDUIT AND WIRING SUPPLIED BY CUSTOMER. Maximum distance between RIM and UPS not to exceed 500 feet.
Page 156
A ---24 CONNECTORS 171.5 (6.75) KNOCKOUTS PROVIDED ON FIVE SURFACES Dimensions are in millimeters (inches) DESCRIPTION: DRAWING NO: REVISION: Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation 285.7 (11.25) 273.1 (10.75) RELAY INTERFACE MODULE SHEET: 164201261---8 DATE: 053099 164291261 Rev.
Page 157
(1.62) 190.5 (7.50) CONDUIT AND WIRING SUPPLIED BY CUSTOMER. MAX. DISTANCE BETWEEN REMOTE MONITOR AND UPS NOT TO EXCEED 500 FEET. Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio 164201261 Rev. F 111503 197.47 (7.75) 88.9 (3.50) DESCRIPTION:...
Page 158
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV Installation and Operation A ---26 164291261 Rev. F 111503...
Page 159
All parts requiring replacement for the Factory Warranty period. If, in the opinion of Powerware, the Unit fails to meet published specifications and the defect is within the terms of this warranty, the Unit will be repaired or replaced at the option of Powerware with no charge for replacement parts. Labor required, to make...
Page 160
This Page Intentionally Left Blank. Powerware BPIII Harsh Environment UPS 50--75 kV W--2 Installation and Operation 164291261 Rev. F 111503...