Figure 8. Terminal Block Bracket - Powerware 5075 kVA Installation & Operation Manual

Harsh environment ups 50–75 kva
Table of Contents

Advertisement

Before installing an RMP , be sure you have prepared the UPS according to the
instructions in Chapter 2.
To install an RMP:
1.
Securely mount the RMP(s).
2.
Install wiring from the RMP using ½-in. conduit through the cable entry panels
in either the top or bottom of the UPS cabinet.
The top entry connection requires installation of ½-in. flexible conduit within the
UPS. Bottom entry connection requires no additional routing of conduit within
the UPS.
3.
In the spare parts kit, locate the RMP adapter cable assembly (see Figure 8).
Mate the DB---9 connector on the back of the terminal block into the DB---9
connector on the Communications Panel of the UPS (see Figure 9). Use two
screws from the spare parts kit to secure the terminal block bracket to the
Communications Panel.
Connect to
Port 1 (DB---9) on
Communications Panel
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio
164201261 Rev. F 111503

Figure 8. Terminal Block Bracket