Product Specifications; System Input - Powerware 5075 kVA Installation & Operation Manual

Harsh environment ups 50–75 kva
Table of Contents

Advertisement

System
Powerware BPIII HE 50
Powerware BPIII HE 62.5
Powerware BPIII HE 75

System Input

Operating Input
Voltage
Operating Input
Frequency Range
Operating Input
Current
Input Current
Harmonic Content
Power Walk-In
Power Factor
Line Surges
Powerware BPIII Harsh Environment UPS 50--75 kVA Installation and Operatio
164201261 Rev. F 111503
The following sections detail the input, output and
environmental specifications for the UPS system.
Models
50 kVA, 40kW
62.5 kVA, 50kW
75 kVA, 60kW
208 VAC for operation from 177 VAC to 229 VAC (60 Hz only)
400 VAC for operation from 340 VAC to 440 VAC (50 Hz only)
480 VAC for operation from 408 VAC to 528 VAC (60 Hz only)
600 VAC for operation from 510 VAC to 660 VAC (60 Hz only)
3 Hz of nominal (60 Hz)
Battery Charge:
125% of full load for overload + battery charge
Actual load + 25% of full load for battery charge
Reduced for Generator:
Adjustable, set to 102%
10% maximum over zero to full load based on 10% THD at full
load (with input filter option installed)
Typically 15---20 second rectifier ramp-up to full utility load
Minimum 0.9
6 kV OC, 3 kA SC per ANSI 62.41 and IEC 801---4

Product Specifications

Notes
50 Hz/60 Hz models
50 Hz/60 Hz models
60 Hz models