POTENTIAL OPERATING ISSUES
Error
Message
Code
49
Input channel cannot be de-
commissioned, because it is
used in the C&E logic. Please
remove the input channel first
from the corresponding output
channel C&E and retry the de-
commission operation.
50
Invalid calibration status.
51
Zero gas calibration failed - zero
signal too low.
52
Zero gas calibration failed - zero
signal too high.
53
Span gas calibration failed -
span signal too low.
54
Span gas calibration failed -
span signal too high.
55
Gas calibration failed - sensor
lifetime exceeded. The sensor
sensitivity has fallen to below
50% of its original value; please
replace the sensor.
Pt. No. 2400M2566_1_EN
Possible Cause
Remedial Action
TPPR will not allow
1. Identify the output channel(s) that the input
the removal of an
channel is linked to.
input from the Cause
2. Modify the Cause and Effect matrix for that
and Effect matrix
channel to remove the input channel.
3. Retry the de-commissioning operation.
Channel requires
1. Please retry the operation.
calibration, or has not
2. If still unsuccessful, on the front panel, press
been successfully
the Accept and Reset buttons together for 10 s,
calibrated
which will restart the COB.
3. If the error has not cleared, if possible cycle
power to the system.
4. Contact your local Service Representative if
the problem persists.
The level at which the
1. For a mA channel, calibration should always
channel is trying to
be done by forcing the output from the sensor
calibrate zero is
where the facility exists. Check the configured
outside the
limits on zero and span gas calibration and
configured limits
ensure that the forced mA value is within the
limits.
2. For a mA channel where the sensor has no
facility to force the output, consult the
manufacturer's instructions and carry out a
calibration at the sensor.
3. For a mV channel, there may be a problem
with the sensor or the calibration gas. Consult
the manufacturer's instructions.
4. Contact your local Service Representative if
the problem persists.
The level at which the
channel is trying to
calibrate zero is
————————//————————
outside the
configured limits
The level at which the
As above.
channel is trying to
calibrate span is
If carrying out a cross calibration, check the
outside the
calculated figure using the sensor
configured limits
documentation.
The level at which the
As above.
channel is trying to
calibrate span is
If carrying out a cross calibration, check the
outside the
calculated figure using the sensor
configured limits
documentation.
TPPR monitors the
1. Contact your local service representative to
performance of mV
schedule a sensor replacement.
sensors relative to
2. When the replacement sensor has been
their first span
fitted, repeat calibration in accordance with the
calibration. If the gas
instructions in chapter 6, using the 'First Span'
response falls below
function.
50% of the original
value this error
occurs.
67
Sys
Sys
Fail
Fault
Relay
Relay
Touchpoint Pro
Operating Manual