3 Touchpoint Pro Introduction

Touchpoint Pro (TPPR) is a Command and Control System designed for the Honeywell Analytics' (and third party) range of
fixed sensors and detectors. It provides constant sensor monitoring with automatic alarm response and notification. Its alarm
levels and responses are fully customisable and all events and errors are logged on a removable SD card for easy archiving.
TPPR is certified to monitor hazardous areas such as Zone 2 Div. 2 via remote Z2D2 enclosures.
TPPR can be used indoors or outdoors, in pollution degrees 2 to 4, and up to IP66, depending on the enclosure that is used.
In addition it can be securely networked and either controlled or monitored via a secure network connection and the
Honeywell PC Configuration software or via the secure Honeywell Webserver browser interface.
Note: Both access methods are optional licensed extras. Please visit the Honeywell website for further information or to
download the Operating Instructions.

3.1 TPPR Access Levels

The table below details the access levels for the Local User Interface (UI). Broadly speaking, an Administrator can
commission modules and configure channels, an Engineer can edit channel configuration and do calibrations and testing,
and an Operator can acknowledge and reset events during normal day-to-day operation. Other users can view current and
historical events and trend data, and generate reports.
TPPR is supplied with a default Administrator level account. For security reasons this password will be attached to the
system Touchscreen. When the system is configured, at least one new Administrator account should be created. The
default Administrator should then log out and then log back in as the new Administrator, and should then delete the
default Administrator account to prevent unauthorized access. The Administrator can create other users with
Administrator level access or lower and the Maintenance Engineer can create users with Engineer level access or lower.
Note: Forgotten or deleted passwords cannot be recovered so it is advisable to keep a copy of the master password in a
secure place or have two Administrator accounts.
Authorised users can carry out the following tasks:
Key: Yes , No  Read only  Engineer and Operator 
Task
Basic System Setup
Change Language
Change My Password
Configuring Channels
Configuring Modules
Configuring System
Diagnostics
Help / User Guides
Licence Management
User Management
View and accept and
reset System Events
Generate Reports
Note: Only Administrators can end another user's active session.
Note: For security reasons some of these tasks are unavailable through PC Configuration and Webserver software. Refer to
the appropriate User Manual for more information.
Note: TPPR's ability to Accept and Reset events can be restricted to authorised users by changing the software settings.
However, remote switches cannot be restricted through software so alternative switch protection methods should be used
where required.
Pt. No. 2400M2566_1_EN
INTRODUCTION
Administrator
Table 1.
TPPR Access Levels
11
Engineer
Operator
Touchpoint Pro
Operating Manual

Advertisement