Configuring
5.3 Configuration of the AS-i slaves
5.3.3

Configuration of the AS-i slaves via the control panel in the TIA Portal

You can also execute the functionality of the "SET" button described in Section
"Configuration of the AS-i slaves using the "SET" button (Page 34)" via the control panel in
STEP 7
When configuring the AS-i slaves over the control panel in TIA Portal, if no slaves are
connected to AS-Interface, the CONFIGURED configuration in the master is deleted along
with the profile definition for proxy slaves (see Section "AS-i proxy slave (Page 42)"). The
AS-i voltage must be present.
5.3.4

Configuration of the AS-i slaves using the PLC program

You can use the PLC program to completely define the configuration of the AS-i slaves.
The command interface of the AS-i master is available for this. You use the No. BA:
Write_overall_configuration (Page 131) command to specify the CONF configuration of the
AS-i slaves in the AS-i master, similarly as when configuring the slave in the TIA Portal.
The No. 07: Store_Actual_Configuration (Page 114) command allows you to save the
ACTUAL configuration as the CONF configuration in the AS-i master, similarly as when
using the "SET" button for this.
36
.
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004