Siemens SIMATIC ET 200SP Manual page 124

As-interface master cm as-i master st 3rk7137-6sa00-0bc1
Hide thumbs Also See for SIMATIC ET 200SP:
Table of Contents

Advertisement

Using the command interface
9.4 Description of the AS-i commands
Table 9- 31
Structure of flag 1 and flag 2
Flag 1
Bit
Meaning
0
Config_OK
1
LDS.0
2
Auto_Address_Assign
3
Auto_Address_Available
4
Configuration_Active
5
Normal_Operation_Active
6
APF
7
Offline_Ready
Table 9- 32
Meaning of the flags
Flag
Config_OK
LDS.0
Auto_Address_Assign
Auto_Address_Available
Configuration_Active
Normal_Operation_Active
APF
Offline_Ready
Periphery_OK
Data_Exchange_Active
Off_Line
AUTO_ADDR_ENABLE
Earth_Fault
EEPROM_OK
EFD Disable
124
Meaning
The flag is set when the CONFIGURED configuration and the ACTUAL configuration
match.
The flag is set when an AS-i slave with address 0 is present. (List of Detected Slaves)
The flag is set if automatic address programming is possible. This means that
AUTO_ADDR_ENABLE = 1 and no "incorrect" AS-i slaves are connected to AS-Interface.
The flag is set if automatic address programming can be performed. This means that one
AS-i slave has failed.
The flag is set in "configuration mode" and reset in "protected operation".
The flag is set when the AS-i master is in "protected operation".
The flag is set when the voltage on the AS-i cable is too low (AS-i Power Fail).
The flag is set if the offline phase is active.
The flag is set if none of the AS-i slaves signal a peripheral fault.
The "Data_Exchange_Active" flag is set when cyclic data exchange is in "protected
operation".
The flag is set if the "OFFLINE" operating status is to be adopted or has already been
adopted.
The flag indicates whether automatic address programming is disabled (BIT = 0) or
enabled (BIT = 1) by the user.
The flag is set if a ground fault has been detected on the AS-i cable.
The flag is set if the test of the internal EEPROM was successful.
The flag indicates whether ground fault detection is enabled (BIT = 0) or disabled
(BIT = 1) by the user.
Flag 2
Bit
Meaning
0
Periphery_OK
1
Data_Exchange_Active
2
Off_Line
3
AUTO_ADDR_ENABLE
4
Earth_Fault
5
EEPROM_OK
6
EFD-ENABLE
7
Reserved
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004