Configuring
5.3 Configuration of the AS-i slaves
Option 1: Selection from the hardware catalog
To configure the AS-i slaves, open the hardware catalog in
STEP 7
STEP 7
In
1. Select a module from the hardware catalog.
2. Drag the module to the network view.
3. Connect the AS-i interface of the module (yellow square in the slave symbol) to the
AS-i interface of the AS-i master (yellow square in the master) or directly to the yellow line
of the AS-i subnet. When a connection is made to the AS-i subnet, a free AS-i address is
automatically assigned in the configuration.
You can change this AS-i address in the properties dialog of the AS-i slave in the "AS-
Interface" area.
STEP 7
1. Open the "Object properties" dialog of the CM AS-i Master ST in the ET 200SP. To do so,
select "Object properties" in the shortcut menu.
2. Click the "Slave configuration" tab (FW V1.1 and higher) in the "Properties..." dialog of the
CM AS-i Master ST (FW V1.1 and higher) to open it.
3. Double-click the desired AS-i address (1A, B, 2A, B, etc.) to open the "Configuration" of
the AS-i slave.
4. Click the "Select" button to open the "Slave selection dialog".
5. Select a slave in this dialog.
Alternatively: Select a slave from the "Module" list box.
Option 2: Reading out an existing AS-i configuration
If an AS-i cable with AS-i slaves is connected to the AS-i master, you can transfer the
connected slaves to the configuration of
addresses other than "0".
Procedure:
1. Switch on the AS-i voltage.
2. Compile the project and download it to the station.
STEP 7
3.
– Right click the AS-i master.
– Select "Hardware detection" in the shortcut menu.
STEP 7
– Select the ET 200SP.
– Open the "Properties" dialog of the CM AS-i Master ST by double-clicking the slot of
– Change to the "Options AS-i slaves" tab.
– Click the "Upload to PG" button.
32
(TIA Portal):
(TIA Portal), you will find the AS-i slaves under "Field devices".
V5.5:
(TIA Portal):
V5.5:
the CM AS-i Master ST, for example.
STEP 7
STEP 7
. The connected AS-i slaves must have
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004
.