Using the command interface
9.4 Description of the AS-i commands
9.4.8

No. 07: Store_Actual_Configuration

Meaning
The following ACTUAL configuration data of all AS-i slaves is obtained from the AS-i master:
● Slave profile (IO, ID, ID2 codes)
● ID1 code
This command saves the obtained ACTUAL configuration data as CONF configuration data
in the non-volatile EEPROM. The List of activated AS-i slaves (LAS) is also loaded into the
List of configured AS-i slaves (LPS).
When this command is executed, the AS-i master switches to the offline phase and then
switches back to "protected operation". The AS-i master restarts.
This command is not executed in "protected operation".
The slave parameter values in volatile memory of the AS-i master and the content of the
non-volatile memory for the parameters are not changed. The "Set_Permanent_Parameter"
command must be executed, if necessary.
Note
Configuration data are overwritten
If you configure the AS-i slaves using HW Config, there is normally no need to use the
command described here.
If you use this command, you will overwrite the respective configuration data that resulted
from SET button configuration or HW Config configuration.
Structure of the job data in the send buffer
Table 9- 18
Structure of the job data in the send buffer
Byte
0
114
Meaning
Command number: 07
H
AS-Interface master CM AS-i Master ST (3RK7137-6SA00-0BC1)
Manual, 07/2017, A5E02655262020A/RS-AD/004