Tektronix ECO8000 Series User Manual page 115

Automatic changeover unit
Hide thumbs Also See for ECO8000 Series:
Table of Contents

Advertisement

ECO8000 Series Automatic Changeover Unit User Manual
More than 40% (OK) indicates the battery power is good.
20% to 40% (WARN) indicates the battery power is getting low and should
be replaced soon.
Less than 20% (LOW) indicates that the battery should be replaced
immediately.
FP LED TEST. Press ENTER to run a test of the front panel LED indicators. Each
LED will be illuminated in the possible colors to verify they are fully functional.
PS<1–2> LOAD TEST . Displays the status of the most recent load test of the
backup power supply. The instrument automatically runs a load test on the backup
supply every 24 hours when Option DPW is installed. Load test not run is
displayed when only one supply is installed. When the test is run, the top line of
the display lists whether the test passed or not and the second line lists the date
and time of the test.