TOPPING UP WITHOUT DRAINING FROM THE COOLING SYSTEM

The quantity of PARCOOL EG Concentrate to be topped up can be estimated with the following formula and/or graph:
Corrections concentrate in measured system towards 50% volume by using PARCOOL EG Concentrate
Example:
PN: 1604 8159 00
Total volume coolant =
Measured concentration =
Top-up volume PARCOOL EG Concentrate without drainage
6,0
5,5
5,0
4,5
4,0
3,5
3,0
2,5
2,0
1,5
1,0
0,5
0,0
4
5
6
7
Engine coolant capacity (liter)
Liter
14
33
Vol %
50-
33
=
8
9
10
11
12
13
Liter PARCOOL EG Concentrate
17
*
14 50
/
=
4,8
In case of expansion tank at low level, this quantity is to be
filled without draining from the cooling system.
1
2
3
4
1. Refractometer indication -20° C (33%)
2. Refractometer indication -22° C
3. Refractometer indication -25° C
4. Refractometer indication -30° C
5
5. Refractometer indication -36° C
14
15
16
- 71 -