V-Net Wiring
On the controller's top side, two V-Net ports operate as COM1 and COM2. V-Net Communications to ODU must land on
COM1. Make sure that polarity is correct.
Use shielded, twisted-pair, 18 AWG cabling to wire. Figure 9 shows a wiring example.
Blue
White
Ethernet Wiring
Two RJ-45 10/100-Mbit Ethernet connectors are labeled PRI (LAN1) for primary, and SEC (LAN2) for secondary. Use a standard Ethernet
patch cable to an Ethernet switch.
The factory-default IP address for PRI is 192.168.1.140. The subnet mask is 255.255.255.0. By default, the SEC (LAN2) port is
disabled.
Note:
The MultiSITE Communications Manager controller is not compatible with a Power-Over-Ethernet (POE) network. Connecting the Controller
on a network segment which carries power may cause the unit to fail. In that event, you must disconnect it from the POE network segment
and power-cycle the unit.
Figure 9: Wiring example.
Due to our policy of continuous product innovation, some specifications may change without notification.
©LG Electronics U.S.A., Inc., Englewood Cliffs, NJ. All rights reserved. "LG" is a registered trademark of LG Corp.
Blue
White
WIRING
Only
ground
shield at
ODU.