5. Type Tests
5. Type Tests
5.1. IEC 61850-3 Type Tests
Test
IEC 61000-4-2
IEC 61000-4-3
IEC 61000-4-4
IEC 61000-4-5
IEC 61000-4-6
IEC 61000-4-8
IEC 61000-4-29
IEC 61000-4-11
IEC 61000-4-12
IEC 61000-4-16
IEC 61000-4-17
IEC 60255-5
IEC 60255-5
Table 5.1. IEC 61850-3 Type Tests
RuggedCom® RuggedSwitch™
Description
Enclosure Contact
ESD
Enclosure Air
Radiated RFI
Enclosure ports
Signal ports
Burst (Fast
D.C. Power ports
Transient)
A.C. Power ports
Earth ground ports
Signal ports
Surge
D.C. Power ports
A.C. Power ports
Signal ports
D.C Power ports
Induced
(Conducted) RFI
A.C. Power ports
Earth ground ports
Magnetic Field
Enclosure ports
D.C. Power ports
Voltage Dips
& Interrupts
A.C. Power ports
Signal ports
Damped Oscillatory
D.C. Power ports
A.C. Power ports
Signal ports
Mains Frequency
Voltage
D.C. Power ports
Ripple on D.C.
D.C. Power ports
Power Supply
Signal ports
Dielectric Strength
D.C. Power ports
A.C. Power ports
Signal ports
H.V. Impulse
D.C. Power ports
A.C. Power ports
Test Levels
+/- 8kV
+/- 15kV
20 V/m
+/- 4kV @ 2.5kHz
+/- 4kV
+/- 4kV
+/- 4kV
+/- 4kV line-to-earth, +/- 2kV line-to-line
+/- 2kV line-to-earth, +/- 1kV line-to-line
+/- 4kV line-to-earth, +/- 2kV line-to-line
10V
10V
10V
10V
40 A/m continuous, 1000 A/m for 1 s
1000 A/m for 1s
30% for 0.1s, 60% for
0.1s, 100% for 0.05s
30% for 1 period, 60% for 50 periods
100% for 5 periods, 100% for 50 periods 2
2.5kV common, 1kV
differential mode @ 1MHz
2.5kV common, 1kV
differential mode @ 1MHz
2.5kV common, 1kV
differential mode @ 1MHz
30V Continuous, 300V for 1s
30V Continuous, 300V for 1s
10%
2kV AC (Fail-Safe Relay output)
2kV AC
2kV DC
5kV (Fail-Safe Relay output)
5kV
5kV
24
RS950G Installation Guide Rev 100
Severity Levels
4
4
RuggedCom-
specified
severity levels.
RuggedCom-
specified
severity levels.
4
4
4
4
3
4
3
3
3
3
RuggedCom-
specified
severity levels.
5
N/A
N/A
N/A
3
3
3
4
4
3
N/A
N/A
N/A
N/A
N/A
N/A
Need help?